Temperature/process controller prompt table, Table 6.4, Ct1a to diag – Watlow Series 988 Family User Manual

Page 48

Advertising
background image

Data Communications with the Watlow Series 988 Family

Temperature/process Controller Prompt Table

986, 987,

988

, 989

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

6.4

Command Summary Series 986-989, Chapter 6

CT1A

Cycle Time

? <sp> CT1A <cr>

S.S. relay or open col:

26

Output 1 PID Set A

= <sp> CT1A <sp> data.2 <cr>

0.0 = Burst firing, or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

CT1B

Cycle Time

? <sp> CT1B <cr>

S.S. relay or open col:

39

Output 1 PID Set B

= <sp> CT1B <sp> data.2 <cr>

0.0 = Burst firing (brSt), or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

CT2A

Cycle Time

? <sp> CT2A <cr>

S.S. relay or open col:

32

Output 2 PID Set A

= <sp> CT2A <sp> data.2 <cr>

0.0 = Burst firing (brSt), or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

CT2B

Cycle Time

? <sp> CT2B <cr>

S.S. relay or open col:

45

Output 2 PID Set B

= <sp> CT2B <sp> data.2 <cr>

0.0 = Burst firing (brSt), or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

DATE

Factory

? <sp> DATE <cr>

xxyy

122

Test Date

xx = week
yy = year

DBA

Deadband

? <sp> DBA <cr>

-999

°

F to 999

°

F

33

PID Set A

= <sp> DBA <sp> data.2 <cr>

-555

°

C to 555

°

C

-999 units to 999 units
Default: 0

°

F, 0

°

C, or 0 units

DBB

Deadband

? <sp> DBB <cr>

-999

°

F to 999

°

F

46

PID Set B

= <sp> DBB <sp> data.2 <cr>

-555

°

C to 555

°

C

-999 units to 999 units
Default: 0

°

F, 0

°

C, or 0 units

DE1A

Derivative

? <sp> DE1A <cr>

0.00 to 9.99 minutes

25

Output 1 PID Set A

= <sp> DE1A <sp> data.2 <cr>

Default: 0.00

DE2A

Derivative

? <sp> DE2A <cr>

0.00 to 9.99 minutes

31

Output 2 PID Set A

= <sp> DE2A <sp> data.2 <cr>

Default: 0.00

DE1B

Derivative

? <sp> DE1B <cr>

0.00 to 9.99 minutes

38

Output 1 PID Set B

= <sp> DE1B <sp> data.2 <cr>

Default: 0.00

DE2B

Derivative

? <sp> DE2B <cr>

0.00 to 9.99 minutes

44

Output 2 PID Set B

= <sp> DE2B <sp> data.2 <cr>

Default: 0.00

DEC1

Decimal Point

? <sp> DEC1 <cr>

0 = Decimal point 0

48

Process Input 1

= <sp> DEC1 <sp> data.2 <cr>

1 = Decimal point 0.0
2 = Decimal point 0.00
3 = Decimal point 0.000
Default: 0

DEC2

Decimal Point

? <sp> DEC2 <cr>

0 = Decimal point 0

56

Process Input 2

= <sp> DEC2 <sp> data.2 <cr>

1 = Decimal point 0.0
2 = Decimal point 0.00
3 = Decimal point 0.000
Default: 0

DEV

Process Deviation

? <sp> DEV <cr>

Difference between SP1 and C1

5

Display Loop (IN 1)

DFL

Default Unit Type

? <sp> DFL <cr>

0 = US units

140

= <sp> DFL <sp> data.2 <cr>

1 = Standard International units

DIAG

Lockout

? <sp> DIAG <cr>

0 = No lockout

120

Diagnostics Menu

= <sp> DIAG <sp> data.2 <cr>

1 = Read only
2 = No read or write
Default: 0

Table 6.4 -

CT1A to DIAG

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)