Ramping controller prompt table, Table 5.6, Er2 to hys3 – Watlow Series 988 Family User Manual

Page 34

Advertising
background image

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

Ramping Controller Prompt Table

981,

982,

983, 984

Data Communications with the Watlow Series 988 Family

Command Summary Series 981-984, Chapter 5

5.6

ER2

Error,

? <sp> ER2 <cr>

0 = No error

n/a

Communications

1 = Transmit buffer overflow
2 = Receive buffer overflow
3 = Framing error
4 = Overrun error
5 = Parity error
6 = Talking out of turn
7 = Invalid reply error
8 = Noise error
20 = Command not found
21 = Prompt not found
22 = Incomplete command line
23 = Invalid character
24 = Number of chars. overflow
25 = Input out of limit
26 = Read only command
27 = Write allowed only
28 = Prompt not active
30 = Request to RUN invalid
31 = Request to HOLD invalid
32 = Command invalid in RUN Mode
33 = Command invalid in HOLD Mode
34 = Output 3 is not an Event
35 = Output 4 is not an Event
38 = Asterisk not allowed
39 = Infinite loop error

ERR

Error,

? <sp> ERR <cr>

0 = Errors latching

607

Latching Enable

= <sp> ERR <sp> data.2 <cr>

1 = Errors non-latching
Default: 1

FTR1

Filter Time Constant ? <sp> FTR1 <cr>

-60 to 60 seconds

604

Process Input 1

= <sp> FTR1 <sp> data.2 <cr>

Default: 0

GSD

Guaranteed Soak

? <sp> GSD <cr>

0°F to 999°F

1205

Deviation

= <sp> GSD <sp> data.2 <cr>

0°C to 999°C
0 to 999 units
0 = (disabled)
Default: 0°F, 0°C, or 0 units

HIP

High Power Limit

? <sp> HIP <cr>

LOP (%) to 100%

714

= <sp> HIP <sp> data.2 <cr>

Default: 100 (heat/cool)
Default: 0 (cool only)

HOLD Simulate HOLD

= <sp> HOLD <sp> data.2 <cr>

1 = Holds current file# and step#

1210

Key Press

HUNT Slidewire

? <sp> HUNT <cr>

0.1% to 100.0%

1905

Dead Band %

= <sp> HUNT <sp> data.2 <cr>

Default: 1.0%

HYS1

Output 1 Hysteresis

? <sp> HYS1 <cr>

0°F to 999°F

507

= <sp> HYS1 <sp> data.2 <cr>

0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C, or 3 units

HYS2

Output 2 Hysteresis

? <sp> HYS2 <cr>

0°F to 999°F

517

= <sp> HYS2 <sp> data.2 <cr>

0°C to 555°C

720

0 units to 999 units
Default: 3°F, 2°C, or 3 units

HYS3

Output 3 Hysteresis

? <sp> HYS3 <cr>

0°F to 999°F

737

= <sp> HYS3 <sp> data.2 <cr>

0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C, or 3 units

Table 5.6 -

ER2 to HYS3

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.
(This does not
apply to Modbus
Protocol.)