Dual channel controller prompt table, Table 7.8, Ot3s to pb2b – Watlow Series 988 Family User Manual

Page 66

Advertising
background image

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

Dual Channel Controller Prompt Table

996, 997,

998

, 999

7.8

Data Communications with the Watlow Series 988 Family

Command Summary Series 996-999, Chapter 7

OT3S

Output 3 Status

? <sp> OT3S <cr>

0 = off

1903

1 = on

OTPT

Lockout Output

? <sp> OTPT <cr>

0 = No lockout

1310

Menu

= <sp> OTPT <sp> data.2 <cr>

1 = Read only
2 = No read or write
Default: 0

OTY1

Output 1 Hardware

? <sp> OTY1 <cr>

0 = None

16
OTY2

Output 2 Hardware

? <sp> OTY2 <cr>

1 = SSR 0.5A

17
OTY3

Output 3 Hardware

? <sp> OTY3 <cr>

2 = SSR 0.5A with suppression

18
OTY4

Output 4 Hardware

? <sp> OTY4 <cr>

5 = Dual SSR Form A

19

6 = Switched dc
7 = Dual Switched dc
8 = Relay 5A Form C
9 = Relay 5A Form C with suppression
10 = Relay 5A Form A/B
11 = Relay 5A Form A/B with suppres-

sion

12 = Dual Relay Form A
13 = Process output
14 = Voltage retransmit
15 = Current retransmit
16 = Power supply
17 = Comms EIA-232
18 = Comms EIA -485 / EIA 422
19 = Comms EIA -485 / EIA-232

PB1A

Proportional Band

? <sp> PB1A <cr>

if DFL = 0 and CF = 1, then 0 to 555°C

500

Output 1 PID

= <sp> PB1A <sp> data.2 <cr>

if DFL = 0 and CF = 0, then 0 to 999°F

Channel A

if DFL = 0 and IN1 = a process value,
then 0 to 999 units
if DFL = 1, then 0.0 to 99.9% of span
Default: 25°F, 14°C, 25 units, or 3.0%

PB1B

Proportional Band

? <sp> PB1B <cr>

if DFL = 0 and CF = 1, then 0 to 555°C

520

Output 1 PID

= <sp> PB1B <sp> data.2 <cr>

if DFL = 0 and CF = 0, then 0 to 999°F

Channel B

if DFL = 0 and IN1 = a process value,
then 0 to 999 units
if DFL = 1, then 0.0 to 99.9% of span
Default: 25°F, 14°C, 25 units, or 3.0%

PB2A

Proportional Band

? <sp> PB2A <cr>

if DFL = 0 and CF = 1, then 0 to 555°C

510

Output 2 PID

= <sp> PB2A <sp> data.2 <cr>

if DFL = 0 and CF = 0, then 0 to 999°F

Channel A

if DFL = 0 and IN1 = a process value,
then 0 to 999 units
if DFL = 1, then 0.0 to 99.9% of span
Default: 25°F, 14°C, 25 units, or 3.0%

PB2B

Proportional Band

? <sp> PB2B <cr>

if DFL = 0 and CF = 1, then 0 to 555°C

530

Output 2 PID

= <sp> PB2B <sp> data.2 <cr>

if DFL = 0 and CF = 0, then 0 to 999°F

Channel B

if DFL = 0 and IN1 = a process value,
then 0 to 999 units
if DFL = 1, then 0.0 to 99.9% of span
Default: 25°F, 14°C, 25 units, or 3.0%

Table 7.8 -

OT3S to PB2B

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 996-999
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)