Dual channel controller prompt table, Table 7.10, Rpa to sys – Watlow Series 988 Family User Manual

Page 68

Advertising
background image

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

Dual Channel Controller Prompt Table

996, 997,

998

, 999

7.10

Data Communications with the Watlow Series 988 Family

Command Summary Series 996-999, Chapter 7

RPA

Ramping Initiation

? <sp> RPA <cr>

0 = off

1100

Channel A

= <sp> RPA <sp> data.2 <cr>

1 = On startup
2 = On startup and set point change
Default: 0

RPB

Ramping Initiation

? <sp> RPB <cr>

0 = off

1104

Channel B

= <sp> RPB <sp> data.2 <cr>

1 = On startup
2 = On startup and set point change
Default: 0

RTA

Ramp Rate

? <sp> RTA <cr>

0 to 9999°/minute

1101

Channel A

= <sp> RTA <sp> data.2 <cr>

Default: 100°/minute

RTB

Ramp Rate

? <sp> RTB <cr>

0 to 9999°/minute

1105

Channel B

= <sp> RTB <sp> data.2 <cr>

Default: 100°/minute

RTD1

RTD Calibration

? <sp> RTD1 <cr>

0 = JIS

609

Curve Input 1

= <sp> RTD1 <sp> data.2 <cr>

1 = DIN
Default: 1

RTD2

RTD Calibration

? <sp> RTD2 <cr>

0 = JIS

619

Curve Input 2

= <sp> RTD2 <sp> data.2 <cr>

1 = DIN
Default: 1

SIL3

Alarm 3 Silence

? <sp> SIL3 <cr>

0 = off / disabled

739

= <sp> SIL3 <sp> data.2 <cr>

1 = on / enabled
Default: 0

SRNB Serial Number

? <sp> SRNB <cr>

xxxx =

2

Bottom Display

0000 to 9999

Read the six-digit unit
serial number in two
segments,
"SNxx" and "xxxx,"
i.e., as in the
upper and lower
front panel displays.

SRNT

Serial Number

? <sp> SRNT <cr>

SNxx =

1

Top Display

00 to 99

SOFT

Software Revision

? <sp> SOFT <cr>

0 = Rev A

7 = Rev H

4

1 = Rev B

8 = Rev I

2 = Rev C

9 = Rev J

3 = Rev D

10 = Rev K

4 = Rev E

11 = Rev L

5 = Rev F

12 = Rev M

6 = Rev G

13 = Rev N
etc.

SPA

Set Point Channel A ? <sp> SPA <cr>

RL1 to RH1

300

= <sp> SPA <sp> data.2 <cr>

Default: per IN1 and hardware

SPB

Set Point Channel B ? <sp> SPB <cr>

RL2 to RH2

319

= <sp> SPB <sp> data.2 <cr>

Default: per IN1 and hardware

SP2A

Set Point 2

? <sp> SP2A <cr>

RL1 to RH1

309

Channel A

= <sp> SP2A <sp> data.2 <cr>

Default: per input range

Heat/Heat or
Cool/Cool Only

SP2B

Set Point 2

? <sp> SP2B <cr>

RL2 to RH2

328

Channel B

= <sp> SP2B <sp> data.2 <cr>

Default: per input range

Heat/Heat or
Cool/Cool Only

SYS

Lockout System

? <sp> SYS <cr>

0 = No lockout

1306

Menu

= <sp> SYS <sp> data.2 <cr>

1 = Read only
2 = No read or write
Default: 0

Table 7.10 -

RPA to SYS

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 996-999
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)