Dual channel controller prompt table, Table 7.3, Atm to date – Watlow Series 988 Family User Manual

Page 61

Advertising
background image

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

996, 997,

998

, 999

Dual Channel Controller Prompt Table

Command Summary Series 996-999, Chapter 7

7.3

Data Communications with the Watlow Series 988 Family

ATM

Auto-Manual Key

? <sp> ATM <cr>

0 = Auto Mode Channels A and B

301

= <sp> ATM <sp> data.2 <cr>

1 = Manual Mode Chan. A, Auto Chan. B
2 = Manual Mode Chan. B, Auto Chan. A
3 = Manual Mode Channels A and B
Default: n/a
Disabled if LOC = 2 or 3

ATSP

Auto-tune

? <sp> ATSP <cr>

50 to 150%

304

Set Point %

= <sp> ATSP <sp> data.2 <cr>

Default: 90%

AUT

Auto-tune

? <sp> AUT <cr>

0 = No auto-tuning

305

= <sp> AUT <sp> data.2 <cr>

1 = Tune Channel A PID
2 = Tune Channel B PID
Default: off

C1

Input 1 Value

? <sp> C1 <cr>

Based on IN1 range ; RL1 to RH1

100

C2

Input 2 Value

? <sp> C2 <cr>

Based on IN2 range ; RL2 to RH2

104

CAL

Lockout

? <sp> CAL <cr>

0 = No lockout

1305

Calibration Menu

= <sp> CAL <sp> data.2 <cr>

1 = Read only
2 = No read or write
Default: 0

CAL1

Input 1 Calibration

? <sp> CAL1 <cr>

-999°F to 999°F

605

Offset

= <sp> CAL1 <sp> data.2 <cr>

-555°C to 555°C
-999 Units to 999 Units
Default: 0

CAL2

Input 2 Calibration

? <sp> CAL2 <cr>

-999°F to 999°F

615

Offset

= <sp> CAL2 <sp> data.2 <cr>

-555°C to 555°C
-999 Units to 999 Units
Default: 0

CF

Degrees Select

? <sp> CF <cr>

0 = Display °F

901

Display Loop

= <sp> CF <sp> data.2 <cr>

1 = Display °C
Default = 0

COM

Lockout Comms

? <sp> COM <cr>

0 = No lockout

1312

Menu

= <sp> COM <sp> data.2 <cr>

1 = Read only
2 = No read or write
Default: 0

CT1A

Cycle Time

? <sp> CT1A <cr>

S.S. relay or open collector:

506

Output 1 PID

= <sp> CT1A <sp> data.2 <cr>

0.9 = Burst firing, or

Channel A

1.0 to 999.9 sec. (Time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 30.0 sec.

CT1B

Cycle Time

? <sp> CT1B <cr>

S.S. relay or open collector:

526

Output 1 PID

= <sp> CT1B <sp> data.2 <cr>

0.9 = Burst firing, or

Channel B

1.0 to 999.9 sec. (Time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 30.0 sec.

CT2A

Cycle Time

? <sp> CT2A <cr>

S.S. relay or open collector:

516

Output 2 PID

= <sp> CT2A <sp> data.2 <cr>

0.9 = Burst firing, or

Channel A

1.0 to 999.9 sec. (Time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 30.0 sec.

CT2B

Cycle Time

? <sp> CT2B <cr>

S.S. relay or open collector:

536

Output 2 PID

= <sp> CT2B <sp> data.2 <cr>

0.9 = Burst firing, or

Channel B

1.0 to 999.9 sec. (Time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 30.0 sec.

DATE

Factory

? <sp> DATE <cr>

xxyy

5

Test Date

xx = Week
yy = Year

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 996-999
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

Table 7.3 -

ATM to DATE

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)