Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

Ramping Controller Prompt Table

981,

982,

983, 984

Data Communications with the Watlow Series 988 Family

Command Summary Series 981-984, Chapter 5

5.10

PTYP

Program Type;

? <sp> PTYP <cr>

0 = Time-based; hour:min:sec

1208

Time-based, or

= <sp> PTYP <sp> data.2 <cr>

1 = Ramp rate-based; °/minute

Ramp rate-based

Default: 0

PWR

Percent Power

? <sp> PWR <cr>

-100% to 100%

103

Present Output

Default: n/a

RA1

Rate Output 1

? <sp> RA1 <cr>

0.00 to 9.99 minutes

504

= <sp> RA1 <sp> data.2 <cr>

Default: 0.00

RA2

Rate Output 2

? <sp> RA2 <cr>

0.00 to 9.99 minutes

514

= <sp> RA2 <sp> data.2 <cr>

Default: 0.00

RE1

Reset Output 1

? <sp> RE1 <cr>

0.00 to 9.99 repeats/min.

502

= <sp> RE1 <sp> data.2 <cr>

Default: 0.10 repeats/min.

RE2

Reset Output 2

? <sp> RE2 <cr>

0.00 to 9.99 repeats/min.

512

= <sp> RE2 <sp> data.2 <cr>

Default: 0.10 repeats/min.

RESU Resume a Program

= <sp> RESU <sp> data.2 <cr>

1 = Resumes current file# and step#

1209

RH1

Range High

? <sp> RH1 <cr>

min. IN1 range to max. IN1 range

603

Input 1

= <sp> RH1 <sp> data.2 <cr>

Default: sensor high range

RH2

Range High

? <sp> RH2 <cr>

min. IN2 range to max. IN2 range

613

Input 2

= <sp> RH2 <sp> data.2 <cr>

Default: sensor high range

RHS

Run/Hold Status

? <sp> <RHS> <cr>

0 = Hold

200

1 = Run
2 = Pre-run

RL1

Range Low

? <sp> RL1 <cr>

min. IN1 range to max. IN1 range

602

Input 1

= <sp> RL1 <sp> data.2 <cr>

Default: sensor low range

RL2

Range Low

? <sp> RL2 <cr>

min. IN2 range to max. IN2 range

612

Input 2

= <sp> RL2 <sp> data.2 <cr>

Default: sensor low range

RTD1

RTD Calibration

? <sp> RTd1 <cr>

0 = JIS

609

Curve Input 1

= <sp> RTd1 <sp> data.2 <cr>

1 = DIN
Default: 1

SIL2

Alarm 2 Silence

? <sp> SIL2 <cr>

0 = off/disabled

722

= <sp> SIL2 <sp> data.2 <cr>

1 = on/enabled
Default: 0

SIL3

Alarm 3 Silence

? <sp> SIL3 <cr>

0 = off/disabled

739

= <sp> SIL3 <sp> data.2 <cr>

1 = on/enabled
Default: 0

SRNB Serial Number

? <sp> SRNB <cr>

xxxx =

2

Bottom Display

0000 to 9999

Read the six-digit
unit serial number
in two segments,
SNxx and xxxx,
i.e., upper and lower
front panel displays.

SRNT

Serial Number

? <sp> SRNT <cr>

SNxx =

1

Top Display

00 to 99

SOFT

Software Revision

? <sp> SOFT <cr>

0 = Rev A

8 = Rev I

4

1 = Rev B

9 = Rev J

2 = Rev C

10 = Rev K

3 = Rev D

11 = Rev L

4 = Rev E

12 = Rev M

5 = Rev F

13 = Rev N

6 = Rev G

etc..........

7 = Rev H

Table 5.10 -

PTYP to SOFT

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.
(This does not
apply to Modbus
Protocol.)

Advertising