Dual channel controller prompt table, Table 7.2, A3hi to arl – Watlow Series 988 Family User Manual

Page 60

Advertising
background image

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

Dual Channel Controller Prompt Table

996, 997,

998

, 999

7.2

Data Communications with the Watlow Series 988 Family

Command Summary Series 996-999, Chapter 7

A3HI

Output 3 Alarm High ? <sp> A3HI<cr>

Process: A3LO to sensor high range

341

= <sp> A3HI <sp> data.2 <cr>

Deviation: 0 to 9999°
Default: RH or 999°

A3LO

Output 3 Alarm Low ? <sp> A3LO <cr>

Process: sensor low range to A3HI

340

= <sp> A3LO <sp> data.2 <cr>

Deviation: -999 to 0°
Default: RL or -999°

ACAL Analog Offset

? <sp> ACAL <cr>

-999 to 999°F

746

= <sp> ACAL <sp> data.2 <cr>

-555 to 555°C
-999 to 999 units
Default: 0°F, 0°C, 0 units

AL3

Alarm 3 Type

? <sp> AL3 <cr>

0 = Process Alarm, Input 2 (CH B)

736

= <sp> AL3 <sp> data.2 <cr>

1 = Deviation Alarm, Input 2 (CH B)
2 = Process Alarm, Input 1 (CH A)
3 = Deviation Alarm, Input 1 (CH A)
Default: 2

ALM

Alarm Status

? <sp> ALM <cr>

0 = No alarms occurring (0000 0000)

110

(Writing a 0 clears

= <sp> ALM <sp> 0 <cr>

Bit 3 = A3LO

(0000 0100)

next alarm.)

Bit 4 = A3HI

(0000 1000)

110 = Alarm 3

0 = off
1 = HI
2 = LO

ALT

Altitude

? <sp> ALT <cr>

0 = 0

1902

Compensation

= <sp> ALT <sp> data.2 <cr>

1 = 2500 feet
2 = 5000 feet
default: 0

AMB

Ambient Terminal

? <sp> AMB <cr>

Input 1 terminals in 0.0°F

1500

Temperature

ANUN Alarm Annunciation ? <sp> ANUN <cr>

0 = off

742

= <sp> ANUN <sp> data.2 <cr>

1 = on
Default: on

AOUT Analog Output 3

? <sp> AOUT <cr>

0 = Retransmit Process Channel A

743

Retransmit Function = <sp> AOUT <sp> data.2 <cr>

1 = Retransmit Set Point Channel A
2 = off
3 = Retransmit Process Channel B
4 = Retransmit Set Point Channel B
Default: 0

ARH

Retransmit

? <sp> ARH <cr>

ARL to 9999

745

Range High

= <sp> ARH <sp> data.2 <cr>

Default: RH1 or RH2 per AOUT

ARL

Retransmit

? <sp> ARL <cr>

-999 to ARH

744

Range Low

= <sp> ARL <sp> data.2 <cr>

Default: RL1 or RL2 per AOUT

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 996-999
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

Table 7.2 -

A3HI to ARL

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

Command Summary Series 996-999 Data Communications