Dual Channel Controller Prompt Table
Command Summary Series 996-999, Chapter 7
7.5
Data Communications with the Watlow Series 988 Family
ER2
Error,
? <sp> ER2 <cr>
0 = No error
n/a
Communications
1 = Transmit buffer overflow
2 = Receive buffer overflow
3 = Framing error
4 = Overrun error
5 = Parity error
6 = Talking out of turn
7 = Invalid reply error
8 = Noise error
20 = Command not found
21 = Prompt not found
22 = Incomplete command line
23 = Invalid character
24 = Number of chars. overflow
25 = Input out of limit
26 = Read only command
27 = Write allowed only
28 = Prompt not active
ERR
Error,
? <sp> ERR <cr>
0 = Errors latching
607
Latching Enable
= <sp> ERR <sp> data.2 <cr>
1 = Errors non-latching
Default: 1
FAIL
Sensor Failure
? <sp> FAIL <cr>
Bumpless = LOP - 1%
902
Output Function
= <sp> FAIL <sp> data.2 <cr>
Heat/cool manual = -100 to 100%
Failure mode can be
Heat only manual = 0% to 100%
bumpless transfer
Cool only manual = -100% to 0%
or manual (% Power)
Default: Bumpless
control. See user’s
manual, Error Code
Actions.
FTR1
Process Input 1
? <sp> FTR1 <cr>
-60 to 60 seconds
604
Filter Time Constant = <sp> FTR1 <sp> data.2 <cr>
Default: 0
FTR2
Process Input 2
? <sp> FTR2 <cr>
-60 to 60 seconds
614
Filter Time Constant = <sp> FTR2 <sp> data.2 <cr>
Default: 0
GLBL
Lockout
? <sp> GLBL <cr>
0 = No lockout
1311
Global Menu
= <sp> GLBL <sp> data.2 <cr>
1 = Read only
2 = No read or write
Default: 0
HY1A
Output 1A Hysteresis ? <sp> HY1A <cr>
0°F to 999°F
507
= <sp> HY1A <sp> data.2 <cr>
0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C or 3 units
HY1B
Output 1B Hysteresis ? <sp> HY1B <cr>
0°F to 999°F
527
= <sp> HY1B <sp> data.2 <cr>
0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C or 3 units
HY2A
Output 2A Hysteresis ? <sp> HY2A <cr>
0°F to 999°F
517
= <sp> HY2A <sp> data.2 <cr>
0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C or 3 units
HY2B
Output 2B Hysteresis ? <sp> HY2B <cr>
0°F to 999°F
537
= <sp> HY2B <sp> data.2 <cr>
0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C or 3 units
HYS3
Output 3 Hysteresis
? <sp> HYS3 <cr>
0°F to 999°F
737
= <sp> HYS3 <sp> data.2 <cr>
0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C or 3 units
Table 7.5 -
ER2 to HYS3
ç
CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 996-999
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)