Temperature/process controller prompt table, Table 6.5, Ei1 to fail – Watlow Series 988 Family User Manual

Page 49

Advertising
background image

Temperature/process Controller Prompt Table

986, 987,

988

, 989

Data Communications with the Watlow Series 988 Family

6.5

Command Summary Series 986-989, Chapter 6

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

EI1

Event Input 1

? <sp> EI1 <cr>

Software Revision

11

Function

= <sp> EI1 <sp> data.2 <cr>

thru M N and later
0

0 = Switch PID Sets

1

1 = None

2

2 = Lock out keyboard

3

3 = Alarm reset

N/A

4 = Auto/manual select

4

5 = Turn control outputs off

5

6 = Reverse Output 1

6

7 = Activate Idle Set Point

7

8 = Activate Remote Set Pt

Default: 1

EI1S

Event Input 1 Status ? <sp> EI1S <cr>

0 = off (open)

104

1 = on (closed)

EI2

Event Input 2

? <sp> EI2 <cr>

Software Revision

12

Function

= <sp> EI2 <sp> data.2 <cr>

thru M N and later
0

0 = Switch PID Sets

1

1 = None

2

2 = Lock out keyboard

3

3 = Alarm reset

N/A

4 = Auto/manual select

4

5 = Turn control outputs off

5

6 = Reverse Output 1

6

7 = Activate Idle Set Point

7

8 = Activate Remote Set Pt

Default: 1

EI2S

Event Input 2 Status ? <sp> EI2S <cr>

0 = off (open)

105

1 = on (closed)

ER

Error, Analog Input

? <sp> ER <cr>

0 = No error

4

(Multiple errors

1 = Input 1 A-D overflow

possible.)

2 = Input 1 overrange
3 = Input 1 underrange
4 = Input 1 A-D underflow
5 = Input 2 A-D overflow
6 = Input 2 overrange
7 = Input 2 underrange
8 = Input 2 A-D underflow
9 = Ambient error
10 = Heater
11 = Open loop

ER2

Error,

? <sp> ER2 <cr>

0 = No error

n/a

Communications

1 = Transmit buffer overflow
2 = Receive buffer overflow
3 = Framing error
4 = Overrun error
5 = Parity error
6 = Talking out of turn
7 = Invalid reply error
8 = Noise error
20 = Command not found
21 = Prompt not found
22 = Incomplete command line
23 = Invalid character
24 = Number of chars. overflow
25 = Input out of limit
26 = Read only command
27 = Write allowed only
28 = Prompt not active

ERR

Error,

? <sp> ERR <cr>

0 = Errors latching

97

Latching Enable

= <sp> ERR <sp> data.2 <cr>

1 = Errors non-latching
Default = 1

FAIL

Sensor Failure

? <sp> FAIL <cr>

Bumpless = LOP - 1%

96

Output Function

= <sp> FAIL <sp> data.2 <cr>

Heat/cool manual = -100 to 100%
Heat only manual = 0% to 100%
Cool only manual = -100% to 0%
Default = Bumpless

Table 6.5 -

EI1 to FAIL

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)

Advertising