Temperature/process Controller Prompt Table

986, 987,

988

, 989

Data Communications with the Watlow Series 988 Family

6.7

Command Summary Series 986-989, Chapter 6

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

IN2

Input 2 Type

? <sp> IN2 <cr>

0 = t/c Low Gain off

55

= <sp> IN2 <sp> data.2 <cr>

1 = J t/c; 32 to 1500

°

F/0 to 816

°

C

2 = K t/c; -328 to 2500

°

F/-200 to 1371

°

C

(Caution: Writing to

3 = T t/c; -328 to 750

°

F/-200 to 399

°

C

IN2 resets most

4 = N t/c; 32 to 2372

°

F/0 to 1300

°

C

prompts to their de-

5 = E t/c; -328 to 1470

°

F/-200 to 799

°

C

fault state.)

6 = C t/c (W3); 32 to 4200

°

F 0 to 2316

°

C

7 = D t/c (W5); 32 to 4200

°

F/0 to 2316

°

C

8 = Pt 2; 32 to 2543

°

F/0 to 1395

°

C

9 = t/c High Gain off
10 = R t/c; 32 to 3200

°

F/0 to 1760

°

C

11 = S t/c; 32 to 3200

°

F/0 to 1760

°

C

12 = B t/c; 1598 to 3300

°

F/870 to 1816

°

C

13 = RTD off
14 = 1

°

RTD (DIN); -328 to 1472

°

F/

-200 to 800

°

C

15 = 0.1

°

RTD (DIN); -99.9 to 999.9

°

F/

-99.9 to 700.0

°

C

16 = Process off
17 = 4-20mA; -999 to 9999 units
18 = 0-20mA; -999 to 9999 units
19 = 0-5V

Î

(dc); -999 to 9999 units

20 = 1-5V

Î

(dc); -999 to 9999 units

21 = 0-10V

Î

(dc); -999 to 9999 units

22 = Millivolts off
23 = 0-50mV

Î

(dc); -999 to 9999 units

24 = 0-100mV

Î

(dc); -999 to 9999 units

26 = Resistance off
27 = Slidewire; 100 to 1200

28 = Potentiometer; 0 to 1200

29 = Heater current off
30 = Heater Current; 0 to 50A
31 = Open loop detect
32 = Event input 2 off
33 = Event input 2 on

INPT

Lockout Input Menu ? <sp> INPT <cr>

0 = No input menu lockout

116

= <sp> INPT <sp> data.2 <cr>

1 = Read only
2 = No read or write allowed
Default: 0

IT1A

Integral for Output 1 ? <sp> IT1A <cr>

0.00 to 99.99 minutes per repeat

24

PID Set A

= <sp> IT1A <sp> data.2 <cr>

Default: 0.00 minutes per repeat

IT2A

Integral for Output 2 ? <sp> IT2A <cr>

0.00 to 99.99 minutes per repeat

30

PID Set A

= <sp> IT2A <sp> data.2 <cr>

Default: 0.00 minutes per repeat

IT1B

Integral for Output 1 ? <sp> IT1B <cr>

0.00 to 99.99 minutes per repeat

37

PID Set B

= <sp> IT1B <sp> data.2 <cr>

Default: 0.00 minutes per repeat

IT2B

Integral for Output 2 ? <sp> IT2B <cr>

0.00 to 99.99 minutes per repeat

43

PID Set B

= <sp> IT2B <sp> data.2 <cr>

Default: 0.00 minutes per repeat

INSP

Cascade

? <sp> INSP <cr>

RL1 to RH1, or

144

Inner SP

if CNTL = 2 (ratio), then 0.0 to 20.0
if CNTL = 3 (differential), then -999 to 999
if ATM = 1, then 0 to 100%
Default: per IN1 and hardware

ITY1

Input 1

? <sp> ITY1 <cr>

0 = None

130

Hardware Type

1 = t/c only
2 = Current
3 = Slide wire
4 = Input off
5 = Universal RTD
6 = Universal high gain t/c
7 = Universal low gain t/c
8 = Universal millivolts
9 = Universal process

Table 6.7 -

IN2 to ITY1

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
(RTD setting)
For JIS curve, go
to rtd1 prompt
after selecting In1.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.

Advertising