Ramping controller prompt table, Table 5.7, Idsp to lat3 – Watlow Series 988 Family User Manual

Page 35

Advertising
background image

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

Ramping Controller Prompt Table

981,

982,

983, 984

Command Summary Series 981-984, Chapter 5

Data Communications with the Watlow Series 988 Family

5.7

IDSP

Idle Set Point

? <sp> IDSP <cr>

RL1 to RH1

308

After Power Outage

= <sp> IDSP <sp> data.2 <cr>

IN1

Input 1 Type

? <sp> IN1 <cr>

1 = J t/c; 32 to 1500°F/0 to 816°C

601

= <sp> IN1 <sp> data.2 <cr>

2 = K t/c; -328 to 2500°F/-200 to 1371°C
3 = T t/c; -328 to 750°F/-200 to 399°C
4 = N t/c; 32 to 2372°F/0 to 1300°C
5 = E t/c; -328 to 1470°F/-200 to799°C
6 = C t/c (W3); 32 to 4200°F 0 to 2316°C
7 = D t/c (W5); 32 to 4200°F/0 to 2316°C
8 = Pt 2; 32 to 2543°F/0 to 1395°C
10 = R t/c; 32 to 3200°F/0 to 1760°C
11 = S t/c; 32 to 3200°F/0 to 1760°C
12 = B t/c; 1598 to 3300°F/870 to 1816°C

Caution: Writing to IN1 or IN2 resets most

14 = 1° RTD (DIN); -328 to 1472°F/-200 to 800°C

prompts to their default values.

15 = 0.1° RTD (DIN); -99.9 to 999.9°F/-99.9 to 700.0°C
17 = 4-20mA; -999 to 9999 units
18 = 0-20mA; -999 to 9999 units
19 = 0-5V

Î

(dc); -999 to 9999 units

20 = 1-5V

Î

(dc); -999 to 9999 units

21 = 0-10V

Î

(dc); -999 to 9999 units

23 = 0-50mV

Î

(dc); -999 to 9999 units

24 = 0-100mV

Î

(dc); -999 to 9999 units

IN2

Input 2 Type

? <sp> IN2 <cr>

26 = Slidewire off

611

= <sp> IN2 <sp> data.2 <cr>

27 = Slidewire; 100 to 1200
32 = Event input 2 off
33 = Event Input 2 on

IT1

Integral for Output 1 ? <sp> IT1 <cr>

0.00 to 99.99 minutes per repeat

501

= <sp> IT1 <sp> data.2 <cr>

Default: 10.00 minutes per repeat

IT2

Integral for Output 2 ? <sp> IT2 <cr>

0.00 to 99.99 minutes per repeat

511

= <sp> IT2 <sp> data.2 <cr>

Default: 10.00 minutes per repeat

ITY1

Input 1

? <sp> ITY1 <cr>

0 = None

8

Hardware Type

1 = t/c only
4 = Input off
5 = Universal RTD
6 = Universal high gain t/c
7 = Universal low gain t/c
8 = Universal millivolts
9 = Universal process

ITY2

Input 2

? <sp> ITY2 <cr>

0 = None

9

Hardware Type

3 = Slidewire
4 = Input off
10 = Event input

LAT2

Alarm 2 Latching

? <sp> LAT2 <cr>

0 = Latching alarms

721

= <sp> LAT2 <sp> data.2 <cr>

1 = Non-latching alarms
Default: 1

LAT3

Alarm 3 Latching

? <sp> LAT3 <cr>

0 = Latching alarms

738

= <sp> LAT3 <sp> data.2 <cr>

1 = Non-latching alarms
Default: 1

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.

NOTE:
(RTD setting)
For JIS curve, go
to rtd1 prompt
after selecting In1.

Table 5.7 -

IDSP to LAT3

Advertising