Dual channel controller prompt table, Table 7.6, In1 to inpt – Watlow Series 988 Family User Manual

Page 64

Advertising
background image

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

Dual Channel Controller Prompt Table

996, 997,

998

, 999

7.6

Data Communications with the Watlow Series 988 Family

Command Summary Series 996-999, Chapter 7

IN1

Input 1 Type

? <sp> IN1 <cr>

1 = J t/c; 32 to 1500°F/0 to 816°C

601

= <sp> IN1 <sp> data.2 <cr>

2 = K t/c; -328 to 2500°F/-200 to 1371°C

(Caution: Writing to

3 = T t/c; -328 to 750°F/-200 to 399°C

IN1 resets most

4 = N t/c; 32 to 2372°F/0 to 1300°C

prompts to their

5 = E t/c; -328 to 1470°F/-200 to 799°C

default state.)

6 = C t/c (W3); 32 to 4200°F 0 to 2316°C
7 = D t/c (W5); 32 to 4200°F/0 to 2316°C
8 = Pt 2; 32 to 2543°F/0 to 1395°C
10 = R t/c; 32 to 3200°F/0 to 1760°C
11 = S t/c; 32 to 3200°F/0 to 1760°C
12 = B t/c; 1598 to 3300°F/870 to 1816°C
14 = 1° RTD (DIN); -328 to 1472°F/

-200 to 800°C

15 = 0.1° RTD (DIN); -99.9 to 999.9°F/

-99.9 to 700.0°C

17 = 4-20mA; -999 to 9999 units
18 = 0-20mA; -999 to 9999 units
19 = 0-5V

Î

(dc); -999 to 9999 units

20 = 1-5V

Î

(dc); -999 to 9999 units

21 = 0-10V

Î

(dc); -999 to 9999 units

23 = 0-50mV

Î

(dc); -999 to 9999 units

24 = 0-100mV

Î

(dc); -999 to 9999 units

IN2

Input 2 Type

? <sp> IN2 <cr>

0 = t/c Low Gain off

611

= <sp> IN2 <sp> data.2 <cr>

1 = J t/c; 32 to 1500°F/0 to 816°C

(Caution: Writing to

2 = K t/c; -328 to 2500°F/-200 to 1371°C

IN2 resets most

3 = T t/c; -328 to 750°F/-200 to 399°C

prompts to their

4 = N t/c; 32 to 2372°F/0 to 1300°C

default states.)

5 = E t/c; -328 to 1470°F/-200 to 799°C
6 = C t/c (W3); 32 to 4200°F 0 to 2316°C
7 = D t/c (W5); 32 to 4200°F/0 to 2316°C
8 = Pt 2; 32 to 2543°F/0 to 1395°C
10 = R t/c; 32 to 3200°F/0 to 1760°C
11 = S t/c; 32 to 3200°F/0 to 1760°C
12 = B t/c; 1598 to 3300°F/870 to 1816°C
14 = 1° RTD (DIN); -328 to 1472°F/

-200 to 800°C

15 = 0.1° RTD (DIN); -99.9 to 999.9°F/

-99.9 to 700.0°C

17 = 4-20mA; -999 to 9999 units
18 = 0-20mA; -999 to 9999 units
19 = 0-5V

Î

(dc); -999 to 9999 units

20 = 1-5V

Î

(dc); -999 to 9999 units

21 = 0-10V

Î

(dc); -999 to 9999 units

23 = 0-50mV

Î

(dc); -999 to 9999 units

24 = 0-100mV

Î

(dc); -999 to 9999 units

INPT

Lockout Input Menu ? <sp> INPT <cr>

0 = No input menu lockout

1309

= <sp> INPT <sp> data.2 <cr>

1 = Read only
2 = No read or write allowed
Default: 0

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 996-999
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the
DEC1, DEC2, IN1
or IN2 setting.

NOTE:
(RTD setting)
For JIS curve, go
to rtd1 prompt
after selecting In1.

Table 7.6 -

IN1 to INPT