Dual channel controller prompt table, Table 7.9, Pida to rl2 – Watlow Series 988 Family User Manual

Page 67

Advertising
background image

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

996, 997,

998

, 999

Dual Channel Controller Prompt Table

Command Summary Series 996-999, Chapter 7

7.9

Data Communications with the Watlow Series 988 Family

PIDA

Lockout Channel A

? <sp> PIDA <cr>

0 = No lockout

1307

PID Menu

= <sp> PIDA <sp> data.2 <cr>

1 = Read only
2 = No read or write
Default: 0

PIDB

Lockout Channel B

? <sp> PIDB <cr>

0 = No lockout

1308

PID Menu

= <sp> PIDB <sp> data.2 <cr>

1 = Read only
2 = No read or write
Default: 0

PRCA Process Range

? <sp> PRCA <cr>

0 = 4-20mA

701

Output Channel A

= <sp> PRCA <sp> data.2 <cr>

1 = 0-20mA
2 = 0-5V

Î

(dc)

3 = 1-5V

Î

(dc)

4 = 0-10V

Î

(dc)

Default: 0

PRCB Process Range

? <sp> PRCB <cr>

0 = 4-20mA

718

Output Channel B

= <sp> PRCB <sp> data.2 <cr>

1 = 0-20mA
2 = 0-5V

Î

(dc)

3 = 1-5V

Î

(dc)

4 = 0-10V

Î

(dc)

Default: 0

PRC3

Process Range

? <sp> PRC3 <cr>

0 = 4-20mA

735

Output 3

= <sp> PRC3 <sp> data.2 <cr>

1 = 0-20mA
2 = 0-5V

Î

(dc)

3 = 1-5V

Î

(dc)

4 = 0-10V

Î

(dc)

Default: 0

RA1A

Rate Output 1

? <sp> RA1A <cr>

0.00 to 9.99 minutes

504

PID Channel A

= <sp> RA1A <sp> data.2 <cr>

Default: 0.00

RA1B

Rate Output 1

? <sp> RA1B <cr>

0.00 to 9.99 minutes

524

PID Channel B

= <sp> RA1B <sp> data.2 <cr>

Default: 0.00

RA2A

Rate Output 2

? <sp> RA2A <cr>

0.00 to 9.99 minutes

514

PID Channel A

= <sp> RA2A <sp> data.2 <cr>

Default: 0.00

RA2B

Rate Output 2

? <sp> RA2B <cr>

0.00 to 9.99 minutes

534

PID Channel B

= <sp> RA2B <sp> data.2 <cr>

Default: 0.00

RE1A

Reset Output 1

? <sp> RE1A <cr>

0.00 to 9.99 repeats/minute

502

PID Channel A

= <sp> RE1A <sp> data.2 <cr>

Default: 0.10 repeats/minute

RE1B

Reset Output 1

? <sp> RE1B <cr>

0.00 to 9.99 repeats/minute

522

PID Channel B

= <sp> RE1B <sp> data.2 <cr>

Default: 0.10 repeats/minute

RE2A

Reset Output 2

? <sp> RE2A <cr>

0.00 to 9.99 repeats/minute

512

PID Channel A

= <sp> RE2A <sp> data.2 <cr>

Default: 0.10 repeats/minute

RE2B

Reset Output 2

? <sp> RE2B <cr>

0.00 to 9.99 repeats/minute

532

PID Channel B

= <sp> RE2B <sp> data.2 <cr>

Default: 0.10 repeats/minute

RH1

Range High

? <sp> RH1 <cr>

min. IN1 range to to max. IN1 range

603

Input 1

= <sp> RH1 <sp> data.2 <cr>

Default: Sensor high range

RH2

Range High

? <sp> RH2 <cr>

min. IN2 range to to max. IN2 range

613

Input 2

= <sp> RH2 <sp> data.2 <cr>

Default: Sensor high range

RL1

Range Low

? <sp> RL1 <cr>

min. IN1 range to to max. IN1 range

602

Input 1

= <sp> RL1 <sp> data.2 <cr>

Default: Sensor low range

RL2

Range Low

? <sp> RL2 <cr>

min. IN2 range to to max. IN2 range

612

Input 2

= <sp> RL2 <sp> data.2 <cr>

Default: Sensor low range

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 996-999
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.

Table 7.9 -

PIDA to RL2

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)