Display_select1,2,3 – Yokogawa AXFA14G/C User Manual

Page 18

Advertising
background image

IM 01E20F12-01E

4-4

4. CONFIGURATION

DISPLAY_SELECT1,2,3:

Table 4.2

DISPLAY_SELECT1, 2, 3

DISPLAY_SELECT 1

DISPLAY_SELECT 2

DISPLAY_SELECT 3

The display content for the display unitís
first line.

The display content for the display unitís
second line.

The display content for the display unitís
third line.

0:Flow Rate(%)
1:Out Value
2:Totalized Flow Rate1
3:Totalized Flow Rate2
4:Totalized Flow Rate3

The factory default setting is 1.

0:Off
1:Flow Rate(%)
2:Out Value
3:Flow Rate(Bar)
4:Totalized Flow Rate1
5:Totalized Flow Rate2
6:Totalized Flow Rate3
7:Tag No
8:Adhesion Check
9:Communication

The factory default setting is 0.

0:Off
1:Flow Rate(%)
2:Out Value
3:Flow Rate(Bar)
4:Totalized Flow Rate1
5:Totalized Flow Rate2
6:Totalized Flow Rate3
7:Tag No
8:Adhesion Check
9:Communication

The factory default setting is 0.

T0402.EPS

DISPLAY_CYCLE:

Specifies the cycle of LCD display. The factory default
setting is 400ms, but if a low temperature environment
makes it difficult to view the display, it is recom-
mended that you set a longer display cycle.

VOLUME_FLOW:

Indicates the current measured value and status as the
primary value (volumetric flow) This parameter is
input to the AI Function Block and the Totalizer
Function Block.

Table 4.3

VOLUME_FLOW

Quality (bit 6-7)

Sub-status (bit 2-5)

Limit (bit 0-1)

Alarm Value

T0403.EPS

2:Good (NC)

0:Ok

0:ok

Normal condition

1:Update Event

9:Maintenance required

0:ok

80:Adhesion Wng

0xA4

81:(Reserved)

1:Uncertain

4:Sensor Conversion Not Accurate

1:low limited or

85:Flow Vel Over

0x49

2:high limited

0x4A

7:Configuration Error

0:ok

82:Auto Zero Wng

0x5C

0:Bad

0:Non specific

0:ok

40:PB O/S Mode

0x00

1:Configuration Error

3:constant

50:Span > 10m/s

0x07

51:Span < 0.1m/s

57:Dens Set Err

71:Meas Mod Set

72:Size Set Err

73:Adh Set Err

3:Device Failure

3:constant

10:uP Fault

0x0F

11:EEPROM Fault

12:A/D(H) Fault

13:A/D(L) Fault

14:A/D(Z) Fault

16:EEPROM Dflt

0:ok

100:Comm uP Fault

0x0C

101:Comm EEPROM Fault

105:Comm Error1

106:Comm Error2

4:Sensor Failure

3:constant

15:Coil Open

0x13

30:Sig Overflow

31:Empty Pipe

33:Adhesion Alm

34:(Reserved)

7:Out of Service

0:ok

41:TB O/S Mode

0x1C

Advertising
This manual is related to the following products: