Parameter lists, 1 physical block parameter list (slot 0), Parameter lists -1 – Yokogawa AXFA14G/C User Manual
Page 59: Physical block parameter list (slot 0) -1

IM 01E20F12-01E
9-1
9. PARAMETER LISTS
9.
PARAMETER LISTS
Note
The Write Mode column indicates the mode in which the parameter is write enabled.
O/S:
Write enabled in O/S mode.
MAN: Write enabled in manual mode.
AUTO:Write enabled in auto mode, manual mode, and O/S mode.
–:
Read only.
9.1
Physical Block Parameter List (Slot 0)
T0901-1.EPS
Index
Parameter
Valid Range
Initial Value
Description
Write
Mode
16
BLOCK_OBJECT
Information on this block such as Block Tag, DD Revision, Execution
Time etc.
–
17
ST_REV
0
The revision level of the static data associated with the function block.
The revision value will be incremented each time a static parameter
value in the block is changed.
–
18
TAG_DESC
Specified at
the time of
order
The user description of the intended application of the block.
Auto
19
STRATEGY
0
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
Auto
0 to 65535
20
ALERT_KEY
0
The identification number of the plant unit.
This information may be used in the host for sorting alarms, etc...
Auto
0 to 255
21
TARGET_MODE
Auto
Set the Target of block mode (MODE_BLK) to Auto or O/S according
to the Write Mode of the parameter to be set or changed.
Auto
The permitted bit
is only available.
22
MODE_
BLK
(DS-37)
Auto
The mode parameter is a structured parameter composed of the
actual mode, the normal mode and the permitted mode.
Actual: Indicates the current operating condition.
Permit: Indicates the operating condition that the block is allowed to take.
Normal: Indicates the operating condition that the block will usually take.
–
Actual
O/S, Auto
–
Permitted
O/S, Auto bit
Auto
–
Normal
The permitted bit
is only available.
23
ALARM_
SUM
(DS-42)
0
The current alert status, unacknowledged status, unreported status
and disabled status of the alarms associated with the function block.
–
Current
0
for future use
–
Unacknowledged
0
for future use
–
Unreported
0
for future use
–
Disabled
Bit7 is only
available.
24
SOFTWARE_REVISION
Revision-number of the software of the field device.
–
25
HARDWARE_REVISION
Revision-number of the hardware of the field device.
–
26
DEVICE_MAN_ID
55 (0x37)
Identification code of the manufacturer of the field device.
–
27
DEVICE_ID
AXF
Manufacturer specific identification of the field device.
–
28
DEVICE_SER_NUM
Serial No.
Serial number of the field device.
Auto
29
DIAGNOSIS
0
Detailed information of the device, bitwise coded. More than one
message possible at once.
–
30
DIAGNOSIS_EXTENSION
0
Additional manufacturer-specific information of the device, bitwise
coded.
–
31
DIAGNOSIS_MASK
0: Not supported
1: Supported
1: Supported
Definition of supported DIAGNOSIS information-bits.
–
32
DIAGNOSIS_MASK_
EXTENSION
0: Not supported
1: Supported
1: Supported
Definition of supported DIAGNOSIS_EXTENSION information-bits.
–
33
DEVICE_CERTIFICATION
No information
Space
Not used for ADMAG AXF
–
34
WRITE_LOCKING
0: Lock
2457: Disabled
2457 (0x999)
If set, no writes from anywhere are allowed, except to clear
WRITE_LOCKING.
Auto