Parameter lists, 1 physical block parameter list (slot 0), Parameter lists -1 – Yokogawa AXFA14G/C User Manual

Page 59: Physical block parameter list (slot 0) -1

Advertising
background image

IM 01E20F12-01E

9-1

9. PARAMETER LISTS

9.

PARAMETER LISTS

Note

The Write Mode column indicates the mode in which the parameter is write enabled.

O/S:

Write enabled in O/S mode.

MAN: Write enabled in manual mode.
AUTO:Write enabled in auto mode, manual mode, and O/S mode.
–:

Read only.

9.1

Physical Block Parameter List (Slot 0)

T0901-1.EPS

Index

Parameter

Valid Range

Initial Value

Description

Write

Mode

16

BLOCK_OBJECT

Information on this block such as Block Tag, DD Revision, Execution
Time etc.

17

ST_REV

0

The revision level of the static data associated with the function block.
The revision value will be incremented each time a static parameter
value in the block is changed.

18

TAG_DESC

Specified at
the time of
order

The user description of the intended application of the block.

Auto

19

STRATEGY

0

The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.

Auto

0 to 65535

20

ALERT_KEY

0

The identification number of the plant unit.
This information may be used in the host for sorting alarms, etc...

Auto

0 to 255

21

TARGET_MODE

Auto

Set the Target of block mode (MODE_BLK) to Auto or O/S according
to the Write Mode of the parameter to be set or changed.

Auto

The permitted bit
is only available.

22

MODE_
BLK
(DS-37)

Auto

The mode parameter is a structured parameter composed of the
actual mode, the normal mode and the permitted mode.

Actual: Indicates the current operating condition.

Permit: Indicates the operating condition that the block is allowed to take.

Normal: Indicates the operating condition that the block will usually take.

Actual

O/S, Auto

Permitted

O/S, Auto bit

Auto

Normal

The permitted bit
is only available.

23

ALARM_
SUM
(DS-42)

0

The current alert status, unacknowledged status, unreported status
and disabled status of the alarms associated with the function block.

Current

0

for future use

Unacknowledged

0

for future use

Unreported

0

for future use

Disabled

Bit7 is only
available.

24

SOFTWARE_REVISION

Revision-number of the software of the field device.

25

HARDWARE_REVISION

Revision-number of the hardware of the field device.

26

DEVICE_MAN_ID

55 (0x37)

Identification code of the manufacturer of the field device.

27

DEVICE_ID

AXF

Manufacturer specific identification of the field device.

28

DEVICE_SER_NUM

Serial No.

Serial number of the field device.

Auto

29

DIAGNOSIS

0

Detailed information of the device, bitwise coded. More than one
message possible at once.

30

DIAGNOSIS_EXTENSION

0

Additional manufacturer-specific information of the device, bitwise
coded.

31

DIAGNOSIS_MASK

0: Not supported
1: Supported

1: Supported

Definition of supported DIAGNOSIS information-bits.

32

DIAGNOSIS_MASK_
EXTENSION

0: Not supported
1: Supported

1: Supported

Definition of supported DIAGNOSIS_EXTENSION information-bits.

33

DEVICE_CERTIFICATION

No information

Space

Not used for ADMAG AXF

34

WRITE_LOCKING

0: Lock
2457: Disabled

2457 (0x999)

If set, no writes from anywhere are allowed, except to clear
WRITE_LOCKING.

Auto

Advertising
This manual is related to the following products: