Yokogawa AXFA14G/C User Manual

Page 65

Advertising
background image

IM 01E20F12-01E

9-7

9. PARAMETER LISTS

T0903-3.EPS

Index

Parameter

Valid Range

Initial Value

Description

Write

Mode

77

MASS_FLOW_DENSITY

Setting of the density for mass-flow rate. This parameter is necessary
in situations where t, kg, g, klb or lb has been selected as the mass
unit in VOLUME_FLOW_UNITS. If a mass unit is selected in
VOLUME_FLOW_UNITS and a value of 0 is set for this parameter,
the setting alarm “57: Density SetErr.” will be displayed. In such a
case, ensure that the density is set correctly.

O/S

0 to 32000

0

78

LIMSW_1_
VALUE_D
(DS-34)

This parameter is used in order to indicate the current input value
selected LIMSW_1_TARGET. If the target alarm occurred the value
is set 1. Refore to LIMSW_1_TARGET.

0: not set,
set exclude 0

0

Value

Value

79

LIMSW_1_TARGET

This parameter selects the input channel used to LIMSW_1_
VALUE_D.

O/S

0: Volume Flow

Value

0

80

LIMSW_1_SETPOINT

Sets the threshold of limitswitch 1. If the value of
LIMSW_1_ACT_DIRECTION is HIGH LIMIT, limit switch 1 turns ON
when LIMSW_1_TARGET has gone beyond LIMSW_1_SETPOINT.
If the value of LIMSW_1_ACT_DIRECTION is LO LIMIT, limit switch
1 turns ON when LIMSW_1_TARGET has gone below
LIMSW_1_SETPOINT. The unit set in LIMSW_1_UNIT applies.

O/S

-10

81

LIMSW_1_ACT_
DIRECTION

Selects the direction of the limit switch 1’s actions:

1: LO LIMIT (Low-limit switch)

2: HIGH LIMIT (high-limit switch)

O/S

0: Low Limit

0: Low Limit
1: High Limit

82

LIMSW_1_HYSTERESIS

Sets the hysteresis of limit switch 1 to be applied for resetting the
LIMSW_1_VALUE_D to OFF after LIMSW_1_TARGET went beyond
LIMSW_1_SETPOINT and LIMSW_1_VALUE_D turned
ON (when used as a high-limit switch), or after LIMSW_1_TARGET
went below LIMSW_1_SETPOINT and LIMSW_1_VALUE_D turned
ON (when used as a low-limit switch).

O/S

0.0

0 or larger.

83

LIMSW_1_UNIT

Indicate the unit set in LIMSW_1_TARGET.

1349: m

3

/h

84

LIMSW_2_
VALUE_D
(DS-34)

This parameter is used in order to indicate the current input value
selected LIMSW_2_TARGET. If the target alarm occurred the value
is set 1. Refore to LIMSW_2_TARGET.

0

0: not set,
set exclude 0

85

LIMSW_2_TARGET

Select the input channel to LIMSW_2_VALUE_D.

O/S

0

0: Volume Flow

Value

86

LIMSW_2_SETPOINT

Sets the threshold of limitswitch 2. If the value of LIMSW_2_ACT_
DIRECTION is HIGH LIMIT, limit switch 2 turns ON when LIMSW_
2_TARGET has gone beyond LIMSW_2_SETPOINT. If the value of
LIMSW_2_ACT_DIRECTION is LO LIMIT, limit switch 2 turns ON
when LIMSW_2_TARGET has gone below LIMSW_2_SETPOINT.
The unit set in LIMSW_2_UNIT applies.

O/S

10

87

LIMSW_2_ACT_
DIRECTION

Selects the direction of the limit switch 2’s actions

0: LO LIMIT (Low-limit switch)

1: HIGH LIMIT (high-limit switch)

O/S

1: High Limit

0: Low Limit
1: High Limit

88

LIMSW_2_HYSTERESIS

Sets the hysteresis of limit switch 2 to be applied for resetting the
LIMSW_2_VALUE_D to OFF after LIMSW_2_TARGET went beyond
LIMSW_2_SETPOINT and LIMSW_2_VALUE_D turned ON
(when used as a high-limit switch), or after LIMSW_2_TARGET
went below LIMSW_2_SETPOINT and LIMS W_2_VALUE_D turned
ON (when used as a low-limit switch).

O/S

0

0 or larger.

89

LIMSW_2_UNIT

Indicate the unit set in LIMSW_2_TARGET.

1349: m

3

/h

90

SWITCH_1_
VALUE_D
(DS-34)

Indicate the value of switch 1, which switches ON and OFF
depending on the digital value of the target input parameter selected
in SWITCH_1_TARGET.

0

0: not set,
set exclude 0

91

SWITCH_1_TARGET

This parameter selects the input channel used to LIMSW_1_
VALUE_D.

O/S

0: Adheshion

Alarm

0: Adheshion Alarm
1: Adhesion Warning

Good

Status

Good

Status

Value

Good

Status