IM 01E20F12-01E

4-6

4. CONFIGURATION

FAIL_TOT:

This is the parameter which defines the fail safe mode
of the Totalizer block. This parameter determines the
operation of the Totalizer block during the occurrence
of input values with bas status.

1 0: RUN

UNCERTAIN: Non Specific, ok

2 1: HOLD

UNCERTAIN: Last Usable Value, const.

3 2: MEMORY

UNCERTAIN: Non Specific, ok

Note: Suppose that SET_TOT = TOTALIZE, MODE_TOT

HOLD.

FAIL_TOT value

TOTAL Status

T0410.EPS

MODE_TOT:

This is the parameter which defines the direction of the
totalization.

0: BALANCED; True arithmetic integration of the

incoming rate values.

1: POS_ONLY; Totalization of positive incoming rate

values only.

2: NEG_ONLY; Totalization of negative incoming rate

values only.

3: HOLD; Totalization stopped.

SET_TOT:

SET_TOT is the parameter in order to assign the
condition to the Totalizer.

0: TOTAILIZE; “Normal” operation of the Totalizer.

1: RESET; Assign value “0” to Totalizer.

2: PRESET; Assign value of PRESET_TOT to
Totalizer.

PRESET_TOT:

This is the parameters in order to define the starting
value to the Totalizer.

TOTAL:

This parameter contains the integrated quantity of the
rate parameter provided by CHANNEL and the
associated status.
The alarm information that a priority is the highest is
set as status.
In case of two or more alarms belonging to the same
sub status are generated, the priority of alarm is so
high that the number of an alarm message is small.
However, as for O/S Mode alarm of Totalizer block
and Physical Block, a priority becomes high most.