IM 01E20F12-01E

9-6

9. PARAMETER LISTS

T0903-2.EPS

Index

Parameter

Valid Range

Initial Value

Description

Write

Mode

33

VOLUME_
FLOW
(DS-33)

Indicates the current measured value and status as the primary
value (volumetric flow).
This parameter is input to the AI Function Block and the Totalizer
Function Block.

Value

Value

0

34

VOLUME_FLOW_UNITS

This parameter is used in order to select the unit for VOLUME_
FLOW, VOLUME_FLOW_LO_LIMIT and VOLUME_FLOW_HI_
LIMIT parameters.

O/S

See the “Unit”
sheet.

Specified at the
time of order

35

VOLUME_FLOW_LO_LIMIT

This parameter is used in order to enter the lower range value for
volumetric flow.

O/S

-11.88 to 11.88 m/s
or -22.68 to 22.68 m/s
The value depends
on a volume flow unit.

Specified at the
time of order

36

VOLUME_FLOW_HI_LIMIT

This parameter is used in order to enter the upper range value for
volumetric flow.

O/S

-11.88 to 11.88 m/s
or -22.68 to 22.68 m/s
The value depends
on a volume flow unit.

Specified at the
time of order

57

SAMPLING_
FREQ
(DS-33)

This parameter is used in order to indicates the field frequency of the
sensor (Sensor specific, must not be downloaded).

75

58

SAMPLING_FREQ_UNITS

This parameter is used in order to selected unit code for
SAMPLING_FREQ parameter.

O/S

1077: Hz

1077: Hz

69

VOLUME_FLOW_FTIME

Setting of the damping time constant to VOLUME_FLOW.
The output to reach 63.2% from 0%.

O/S

0.1 to 200.0

3.0

70

DUAL_FREQUENCY_
MODE

Selection of excitation mode.
This parameter is effective when FLOW_TUBE is “ADMAG AXF”
and NOMINAL_SIZE is in between 25mm to 200mm.
Outside the field of that condition, the warning “71:Meas Mod Set”
will be displayed.

O/S

0: Standerd DF
1: Enhanced DF

0: Standard DF

71

LOW_MF

This parameter is used in order to set the low-frequency meter factor.
This setting is linked with that of parameter CALIBR_FACTOR.

O/S

0.01 to 3.0000

1.0000

72

HIGH_MF

This parameter is used in order to set the high-frequency meter
factor.

O/S

0.01 to 3.0000

1.0000

73

LOW_MF_EDF

This parameter is used in order to set the low-frequency meter factor
as required when Enhanced DF (i.e., enhanced dual frequency
excitation) is selected. If “Standard DF” has been selected for
Measure_Mode, neither Low_MF(EDF) nor High_MF(EDF) is
displayed.

O/S

0 to 3.0000

1.0000

74

HIGH_MF_EDF

This parameter is used in order to set the high-frequency meter
factor as required when Enhanced DF (i.e., enhanced dual
frequency excitation) is selected.

O/S

0 to 3.0000

1.0000

75

SELECT_FLOW_TUBE

This parameter is used in order to set the types of flow tube.
When combining this product with an AXF Remote Flow tube,
“ADMAG AXF” should be selected.

O/S

0: ADMAG AXF
1: ADMAG
2: ADMAG AE
3: ADMAG SE
4: YEWMAG
5: Calibrator
6: Other

0: ADMAG

AXF

76

DENSITY_UNIT

This parameter selects the units for density as required when making
settings using Mass_Density.

O/S

1097: kg/m

3

1108: lb/gal
1107: lb/cf

1097: kg/m

3

59-68 reserved by PNO

Status

Good

Status

Good

32

O/S

NOMINAL_SIZE_UNITS

Specified at the
time of order

1013: mm
1019: inch

This parameter is used in order to select the unit of size (diameter)
of the sensor (flow tube).