Yokogawa AXFA14G/C User Manual

Page 67

Advertising
background image

IM 01E20F12-01E

9-9

9. PARAMETER LISTS

T0903-5.EPS

Index

Parameter

Valid Range

Initial Value

Description

Write

Mode

111

DISPLAY_SELECT1

This parameter is used in order to set the LCD display mode.

Auto

1: Out Value

0 to 4

112

DISPLAY_SELECT2

Auto

0: Off

0 to 9

113

DISPLAY_SELECT3

Auto

0: Off

0 to 9

114

DISPLAY_CYCLE

Auto

1: 400ms

This parameter is used in order to set the renewal cycle of LCD
display.
Renewal cycle: 200 msec “DISPLAY_CYCLE”

0: 200ms
1: 400ms
2: 1s,
3: 2s,
4: 4s,
5: 8s

115

LANGUAGE

Auto

0: English

0: English

116

RATE_LIMIT

O/S

5

This parameter is used in order to set the rate limit value.

0 to 10

117

DEAD_TIME

O/S

0

This parameter is used in order to set the time for application of the
rate limit, and if a value of 0 is set, the rate limit function will be
terminated.

0 to 15

118

PULSING_FLOW

O/S

0: No

This parameter is used in order to set the pulsing flow support.

0: No
1: Yes

119

POWER_SYNCH

O/S

1: Yes

This parameter is used in order to indicate whether or not the
internal frequency is to be synchronized with that of the power supply.

0: No
1: Yes

120

POWER_FREQUENCY

O/S

50

This parameter is used in order to set the power frequency.

47.00 to 63.00

121

SOFTWARE_REV_NO

This parameter is used to display the software revision number.

122

ADHESION_CHECK

O/S

0: No

This parameter selects whether or not the adhesion diagnostic
function will be carried out.

NOTE

If the judgment value for Level 3 is exceeded, a warning is displayed;
and if the value for Level 4 is exceeded, an alarm is displayed.

0: No
1: Yes

123

ADHESION_LEVEL1

O/S

0.10

This parameter is used in order to set the resistance value for
judgment of Level 1.

0.00 to 100.00

124

ADHESION_LEVEL2

O/S

0.50

This parameter is used in order to set the resistance value for
judgment of Level 2.

0.00 to 100.00

125

ADHESION_LEVEL3

O/S

1.00

This parameter is used in order to set the resistance value for
judgment of Level 3.

0.00 to 100.00

126

ADHESION_LEVEL4

O/S

3.00

This parameter is used in order to set the resistance value for
judgment of Level 4.

0.00 to 100.00

127

ADH_MEASURE_VALUE

This parameter displays the value measured using the adhesion
diagnostic function.

0.00 to 1000.00