9. PARAMETER LISTS

T0904-2.EPS

Index

Parameter

Valid Range

Initial Value

Description

Write

Mode

32

PRESET_TOT

This parameter is used in order to define the starting value to the
totalizer.

Auto

-99999999 to
+99999999

0 or larger

0.000

33

ALARM_HYS

Amount the PV must return within the alarm limits before the alarm
condition clears. Alarm Hysteresis is expressed as a percent of the
PV span.

Auto

0.000

34

HI_HI_LIM

The setting for high high alarm in engineering units.

The setting for high alarm in engineering units.

The setting of the low alarm in engineering units.

The setting of the low low alarm in engineering units.

Auto

max. Value

+INF

35

HI_LIM

Auto

max. Value

+INF

36

LO_LIM

Auto

min. Value

-INF

37

LO_LO_LIM

Auto

min. Value

-INF

This parameter is used in order to set the state of the upper limit of
alarms.
This parameter contains the state of the upper limit of an alarm and
the related time stamp. The time stamp expresses the time the
measured variable has been equal or higher than the upper limit of
the alarm.

38

HI_HI_ALM
(DS-39)

0

Unacknow-
ledged

0

Alarm State

0: No alarm
Alarm active
exclude 0

0

Time_Stamp

0

Subcode

0

Value

This parameter is used in order to set the state of the upper limit of
warnings.
This parameter contains the state of the upper limit of a warning and
the related time stamp. The time stamp expresses the time the
measured variable has been equal or higher than the upper limit of
the warning.

39

HI_ALM
(DS-39)

0

Unacknow-
ledged

0

Alarm State

0: No alarm
Alarm active
exclude 0

0

Time_Stamp

0

Subcode

0

Value

This parameter is used in order to set the state of the lower limit of
warnings.
This parameter contains the state of the lower limit of a warning and
the related time stamp. The time stamp expresses the time at which
the measured variable has been equal to or lower than the lower
limit of the warning.

40

LO_ALM
(DS-39)

0

Unacknow-
ledged

0

Alarm State

0: No alarm
Alarm active
exclude 0

0

Time_Stamp

0

Subcode

0

Value

This parameter is used in order to set the state of the lower limit of
alarms.
This parameter contains the state of the lower limit of an alarm and
the related time stamp. The time stamp expresses the time at which
the measured variable has been equal to or lower than the lower
limit of the alarm.

41

LO_LO_ALM
(DS-39)

0

Unacknow-
ledged

0

Alarm State

0:No alarm
Alarm active
exclude 0

0

Time_Stamp

0

Subcode

0

Value

For commissioning and test purposes the input value from the
Transducer Block in the Totalizer Function Block, TOT-FB can be
modified when the hardware simulation jumper is on. That means
that the Transducer and TOT-FB will be disconnected.

52

SIMULATE
(DS-50)

42-51 reserved by PNO

0

Simulate_
Status

Auto

View objects allow the following groups of physical block parameter
values to be read with one read request.

ST_REV, MODE_BLK, ALARM_SUM, TOTAL

53

VIEW_TOTALIZER_FB

Auto

0

Simulate_
Value

Auto

0: Disabled,
Enable exclude 0

0: Disabled

Simulate_
Enabled