2 master settings, 3 integration of gsd, Master settings -2 – Yokogawa AXFA14G/C User Manual

Page 9: Integration of gsd -2

Advertising
background image

IM 01E20F12-01E

3-2

3. GETTING STARTED

3.2 Master Settings

To activate PROFIBUS PA, the following bus param-
eters must be set for the master.

IMPORTANT

Do not turn off the power immediately after
setting. When the parameters are saved to the
EEPROM, the redundant processing is executed
for an improvement of reliability. If the power is
turned off within 60 seconds after setting is
made, the modified parameters are not saved
and the settings may return to the original
values.

Table 3.2 Bus Parameters

The maximum time a master
station must wait for the
complete reception of the
first octet of a response (11
bits).
e.g: 4095

Sets the minimum time at
which a slave can send the
first bit of a response back.

Sets the maximum time at
which a slave can send the
first bit of a response back.

Controls the time at which
the bus electronics or
software of the sender is set
to receive mode after a
message is sent.

Sets the maximum allowable
time for parameter setting
and response by the slave.

Sets the number of token
cycles after which the
master will search for a new
master.

Sets the number of retries
that are performed after a
receiver does not respond to
a message.

Sets the highest station
address in the network.

The transmission rate of
PROFIBUS PA matches that
of the segment coupler.
e.g P+F: 93.75 kbps,
Siemens: 45.45 kbps

Description and Settings

Transmission
rate

T

SL

min T

SDR

max T

SDR

T

SET

G

max. retry
limit

HSA

T

QUI

Transmission
Rate

Slot Time

Min. Station
Delay Timer

Max. Station
Delay Time

Setup Time

Gap update
factor

Max Retry
Limit

Highest Station
Address

Quiet Time

Symbol

Parameter

T0302.EPS

3.3 Integration of GSD

A PROFIBUS PA system requires a GSD file
containing device parameters such as the supported
transmission rate, input data, output data, data format
and data length.
The following GSD files are available for the AXF.

Table 3.3 GSD files

PA139740.GSD (AIx1, TOTx1)

0x9740

Profile GSD file

0x4590

Device Specific Ident-Number

YEC_4590.GSD

Device Specific GSD file

Profile Ident-Number

T0303.EPS

Download GSD for AXF from the following website.
http://www.yokogawa.com/fld/doc/profibus/

IMPORTANT

Do not change contents in the GSD file from the
factory default. The AXF may be given a serious
problem in its operation if do so.

Advertising