Yokogawa AXFA14G/C User Manual

Page 43

Advertising
background image

IM 01E20F12-01E

5-19

5. EXPLANATION OF BASIC ITEMS

Warning Message

On the Integral LCD indicator, following messages are
displayed when warning is generated.

Table 5.6.6 Warning Message Display

Category

Display Message

Warning

T0514.eps

80:Adhesion Wng

Slight adhesion to electrodes.

82:Auto Zero Wng

Results of automatic zero adjustment are higher than the rated values.

84:Disp Over Wng

Overflow in the display digits during instantaneous flow rate display.

Display at the LCD indicator only.

85:Flow Vel Over

Flow velocity overflow.

140:Sim.Jmpr On

Simulation jumper is ON.

141:PB Sim. Enabled

PB.DIAGNOSIS_SIM_MODE is enabled.

142:TB VF Sim. Enabled TB.SIMULATE_MODE is ON (Volume Flow Value).

143:AI Sim. Enabled

AI.SIMULATE is enabled.

144:Total1 Sim. Enabled

TOTAL1.SIMULATE is enabled.

145:Total2 Sim. Enabled

TOTAL2.SIMULATE is enabled.

146:Total3 Sim. Enabled

TOTAL3.SIMULATE is enabled.

147:DI1 Sim. Enabled

DI1.SIMULATE is enabled.

148:DI2 Sim. Enabled

DI2.SIMULATE is enabled.

150:AI FB Man Mode

AI.TARGET_MODE is Manual mode.

151:Total1 FB Man Mode TOTAL1.TARGET_MODE is Manual mode.

152:Total2 FB Man Mode TOTAL2.TARGET_MODE is Manual mode.

153:Total3 FB Man Mode TOTAL3.TARGET_MODE is Manual mode.

154:DI1 FB Man Mode

DI1.TARGET_MODE is Manual mode.

155:DI2 FB Man Mode

DI2.TARGET_MODE is Manual mode.

Description

Auto Zero Display

When ZERO_POINT_ADJUST is executed, the
following is displayed until auto zeroing finishes.

A

o

N

w

o

Z e r

u t o

i n

c u t

e

E x

g . . .

F0521.eps

Advertising