4. CONFIGURATION

OUT_D:

OUT_D is the output of the function block. The value
is specified by the operator in MODE MAN.

The relationship between OUT_D.Status and the result
of the DIAGNOSIS are described as below.

The alarm information that a priority is the highest is
set as status.

In case of two or more alarms belonging to the same
sub status are generated, the priority of alarm is so
high that the number of an alarm message is small.
However, as for O/S Mode alarm of DI function block
and Physical Block, a priority becomes high most.

Table 4.8

OUT_D

2:Good (NC)

0:Ok

0:ok

1:Update Event

1:low limited

2:Active Advisory Alarm

2:high limited

3:Active Critical Alarm:

3:constant

4:Unack. Update Event

5:Unack. Advisory Alarm

6:Unack. Critical Alarm

9:Maintenance required

0:ok

80:Adhesion Wng

0xA4

81:(Reserved)

1:Uncertain

0:Non specific

0:ok

82:Auto Zero Wng

0x40

1:low limited or

85:Flow Vel Over

0x41

2:high limited

0x42

0:Bad

0:Non specific

3:constant

50:Span > 10m/s

0x03

51:Span < 0.1m/s

57:Dens Set Err

71:Meas Mod Set

72:Size Set Err

73:Adh Set Err

3:Device Failure

3:constant

10:uP Fault

0x0F

11:EEPROM Fault

12:A/D(H) Fault

13:A/D(L) Fault

14:A/D(Z) Fault

16:EEPROM Dflt

0:ok

100:Comm uP Fault

0x0C

101:Comm EEPROM Fault

105:Comm Error1

106:Comm Error2

4:Sensor Failure

3:constant

15:Coil Open

0x13

30:Sig Overflow

31:Empty Pipe

33:Adhesion Alm

34:(Reserved)

7:Out of Service

0:ok

41:TB O/S Mode

0x1C

3:constant

40:PB O/S Mode

0x1F

46:DI1FB O/S Mode

47:DI2FB O/S Mode

Quality (bit 6-7)

Limit (bit 0-1)

Alarm Value

Sub-status (bit 2-5)

T0409.EPS