9. PARAMETER LISTS

9.4

Totalizer Block Parameter List (TOT1: Slot2, TOT2: Slot3,TOT3: Slot4)

T0904-1.EPS

Index

Parameter

Valid Range

Initial Value

Description

Write

Mode

16

BLOCK_OBJECT
(DS-32)

Information on this block such as Block Tag, DD Revision, Execution
Time etc.

17

ST_REV

The revision level of the static data associated with the function
block. The revision value will be incremented each time a static
parameter value in the block is changed.

0

18

TAG_DESC

The user description of the intended application of the block.

Auto

Space

19

STRATEGY

The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.

Auto

0 to 65535

0

20

ALERT_KEY

The identification number of the plant unit. This information may be
used in the host for sorting alarms, etc.

Auto

0 to 255

0

21

TARGET_MODE

Set the Target Auto, Man or O/S according to the Write Mode of the
parameter to be set or changed.

Auto

The permitted bit is
only available.

Auto

22

MODE_BLK
(DS-37)

The mode parameter is a structured parameter composed of the
actual mode, the normal mode and the permitted mode.

Actual: Indicates the current operating condition.

Permit: Indicates the operating condition that the block is allowed

to take.

Normal: Indicates the operating condition that the block will

usually take.

Auto

Actual

Value

Man

0

Status

Man

0

This parameter contains the integrated quantity of the rate
parameter provided by CHANNEL and the associated status.

O/S, Man,
Auto

O/S bit, Man bit,
Auto bit.

Permitted

Auto

The permitted bit is
only available.

Normal

23

ALARM_SUM
(DS-42)

The current alert status, unacknowledged status, unreported status
and disabled status of the alarms associated with the function block.

Bit1, 2, 3, 4, 7 are
available.

0

Current

0

Unacknow-
ledged

0

Unreported

0

for future use

for future use

for future use

Disabled

24

BATCH
(DS-67)

25

Not used

26

TOTAL
(DS-33)

O/S

1549:Ml, 1034:m

3

,

1517:kL, 1041:hL,
1038:L, 1040:mL,
1035:dm

3

,

1036:cm

3

, 1092:t,

1091:Mg, 1088:kg,
1089:g, 1090:mg,
1043:CF,
1048:gallon,
1051:bbl 1641:bbl
(US federal),
1094:lb

1034:m

3

This parameter is used in order to set the unit of the totalized
quantity.
The unit must be compatible to VOLUME_FLOW_UNITS.
Set UNIT_TOT to a mass unit when a mass unit is set into
VOLUME_FLOW_UNITS.
If the mismatch units are set, the alarm of "120:Total1 Unit Set Err",
"121:Total2 Unit Set Err" or "122:Total3 Unit Set Err" will be
displayed.

27

UNIT_TOT

O/S

273

273

Reference to the active Transducer Block which provides the
measurement value to the Function Block.

28

CHANNEL

Auto

0: TOTALIZE
1: RESET
2: PRESET

0: TOTALIZE

This parameter is used in order to assign the condition to the
totalizer.

29

SET_TOT

O/S

0: BALANCED
1: POS_ONLY
2: NEG_ONLY
3: HOLD

0: BALANCED This parameter is used in order to define how the totalizer counts.

30

MODE_TOT

This parameter is intended to be used in Batch applications in line
with IEC 61512.

Auto

0

BATCH_ID

Auto

0

RUP

Auto

0

OPERATION

Auto

0

PHASE

31

FAIL_TOT

This parameter is used in order to define error response in the event
of the device error or bad measured value.

O/S

0: RUN
1: HOLD
2: MEMORY

0: RUN