1 transducer block, Transducer block -6 – Yokogawa AXFA14G/C User Manual

Page 49

Advertising
background image

IM 01E20F02-01E

6-6

6.3.1 Transducer Block

The configuration of transducer block for this function is shown at Figure 6.3.2. It is necessary to set parameters as
shown in Table 6.3.1 when the simulation function is used.

off

on

F0603.EPS

Sensor

Signal

Conditioning

Signal

processing,

normalization

Unit and limit

computation

Sensor data

(e.g. nominal

size)

Process data

(e.g. low flow

cut)

Units

Limits

Flow Transducer Block

Operator

SIMULATE

_MODE

Totalizer

Analog input

SIMULATE

_TIME

SIMULATE

_TYPE

SIMULATE

_VOLME_FLOW

SIMULATE

_UP_VALUE

SIMULATE

_LO_VALUE

Fixed

2 point
3 point

Ramp

Figure 6.3.2

Configuration of Simulation function in the Transducer block

Table 6.3.1 Simulation parameters in the Transducer Block

T0603.EPS

Index

Parameters

Description

96

SIMULATE_MODE

Select “1: Volume Flow” when the
simulation function is used.

Set the SIMULATE TYPE.

Set the value to be simulated.

97

SIMULATE_TYPE

98

SIMULATE_VOLUME
_FLOW

99

SIMULATE_UP_VALUE Set the simulated upper value when

SIMULATE_TYPE is selected as
1, 2 or 3.

100

SIMULATE_LO_VALUE Set the simulated lower value when

SIMULATE_TYPE is selected as
1, 2 or 3.

Valid Range

0: Off
1: Volume Flow

0: Fixed,
1: 2 points,
2: 3 points,
3: Ramp

None
(Treated as
VOLUME_FLOW
_UNITS)

Except
SIMULATE_LO_
VALUE

Except
SIMULATE_UP_
VALUE

Initial Value

0: Off

0: Fixed

Value: 0,
Status: Good

0

0

101

SIMULATE_TIME

Show the time to maintain a constant
value when SIMULATE_TYPE is
selected as 1 or 2.
When SIMULATE_TYPE is selected
as 3, show the time to maintain a
constant change.

Except 0

30 Sec

Advertising