6.3.2 AI / TOT / DI Blocks

When the parameters are set in the transducer block, it is necessary to set parameters as shown in Table 6.3.2 in the
AI, TOT and DI blocks next. When Simulate_Enabled in each function block described at Table 6.3.2 is set to “1:
Enabled”, the applicable function block uses the simulation value set in this parameter instead of the data from the
transducer block.

Table 6.3.2

Simulation parameters in the AI, TOT and DI Blocks

T0604.EPS

Sub-

index

Parameters

Description

1

Simulate_Status

Set the data status to be simulated.

Set the value of the data to be
simulated.

Controls the simulation function of
this block.

2

Simulate_Value

3

Simulate_Enabled

Valid Range

Unsigned8

Float

0: Disabled,
1: Enabled

Initial Value

0

0

0: Disabled

6.3.3 Physical Block

It is also necessary to set alarms as diagnosis in the Physical block at the same time when the simulation function is
used. The Figure 6.3.3 shows the configuration of alarm for simulation function and the Table 6.3.3 is described its
parameter setting.

off

enabled

on

F0604.EPS

Operator

PB.DIAGNOSIS_
SIM_ENABLED

PB.DIAGNOSIS
SIM_EXENSION

PB.DIAGNOSIS_
MSK

PB.DIAGNOSIS
MSK_EXENSION

PB.DIAGNOSIS

PB.DIAGNOSIS_
EXENSION

TB.ALARM_
PERFORM

Alarms,

Warning

Alarms,

Warning

Figure 6.3.3

Configuration of simulated alarm in the Physical block