2. sc202s 2-wire conductivity transmitter, Quality inspection standards, Sc202s 2-wire conductivity transmitter – Yokogawa EXA SC202 2-Wire Conductivity Transmitter/Analyzer User Manual

Page 93

Advertising
background image

IM 12D08B02-01E

Appendix 3-5

13-2. SC202S 2-Wire Conductivity Transmitter

Quality
Inspection
Standards

SC202S
2-Wire Conductivity Transmitter

QIS 12D08B02-21E

1st Edition: Mar. 2007(YK)

1. Scope

This inspection standard applies to the SC202

2-Wire Conductivity Transmitter.

2. Inspection

Items

2.1 Insulation resistance test

* 2.2 Dielectric strength test

2.3 Current output test

2.4 Temperature indication check

2.5 Resistance (conductivity) check

Note: Items marked with an asterisk (*) may only be confirmed by a test certificate.

3.

Inspection Methods, Standards and Conditions

z

Connect the testing circuit as shown in Figure 1. Allow the instrument to warm up for at least

5 minutes before conducting the tests. For the connections for the insulation resistance test,

follow the instructions in Section 3.1 and for the connections for the dielectric strength test,

follow the instructions in Section 3.2.

z

Performance tests should be done in the inspection mode where the tests from Section 3.3

through Section 3.5 take place in sequence and cannot be retraced. If the reconfirmation of

a test is needed, turn off the power to the transmitter, turn on the power again, and enter the

inspection mode to restart the tests.

z

Set the equipment as follows.

Decade resistance box 1 (temperature): 960.9 :

Decade resistance box 2 (conductivity): 10 :

DC source:

24 VDC

3.1 Insulation Resistance Test

(1) Apply 500 V DC between the power supply terminals shorted together (+ and –) and the

earth terminal (G). The insulation resistance must be 100 MΩ or greater.

(2) Apply 500 V DC between the input terminals shorted together (11 to 16) and the earth

terminal (G). The insulation resistance must be 100 MΩ or greater.

3.2 Dielectric strength test

Apply 600 V AC, an AC voltage of substantially sinusoidal waveform with a frequency of 50 Hz

or 60 Hz, between the terminals shown below, for at least 2 seconds. The insulation must

withstand this voltage. (The sensed current should be 10 mA.)
(1) Between the power supply terminals shorted together (+ and –) and the earth terminal (G)
(2) Between the input terminals shorted together (11 to 16) and the earth terminal (G)
(3) Between the input terminals shorted together (11 to 16) and the power supply terminals

shorted together (+ and –)

3.3 Current Output Test

<Test>

(1) Enter Service Code 87 and then password 070.

(2) When the message display shows “*HIF”, press the [YES] key.

Advertising