SUMMIT 8800

STREAM CONFIGURATION

06

6 .7 .2 Advanced

Figure 96 Stream temperature advanced options

Optional parameters in case there is more than one transmitter in this range:

Average deviation

Deviation that one transmitter may have from the average of all

transmitters before an alarm is raised.

Deviation

The minimum deviation between the transmitters before an alarm is raised.

Deviation time

The time during which the (previous) deviation exists before an alarm is

raised.

Hysteresis for alarms and warnings to prevent continuous switching:
Hysteresis max/min

The value which must be exceeded to switch an alarm on or off.

Hysteresis hi/lo

The value which must be exceeded to switch an warning on or off.

When Hart transmitters are used, then a check on its units can be set
HART unit alarm

Determines if an alarm should be raised when a temperature HART

transmitter reports another unit than defined for the transmitter

HART unit correct

Determines if the temperature Hart units should be used instead of the

configured units.

Determine what to do with the accountable alarms:
Maximum alarm

Raise an alarm when the transmitter range limits are exceeded or not.

Default: Yes.

Minimum alarm

Raise an alarm when the transmitter range limits are exceeded or not.

Default: Yes.