5 .1 .6 .1 pulse output – KROHNE Summit 8800 Vol 2 User Manual
Page 57

57
www.krohne.com
08/2013 - MA SUMMIT 8800 Vol2 R02 en
SUMMIT 8800
HARDWARE DETAILS
05
Figure 33 Configure digital output
Select the desired output
Define the output type as follows
Off
Not used
Pulse
Set to generate pulses to the output for e.g. telemetry
Alarm
Alarm indication to e.g. a alarm horn or a scada system
State
Output set to on or off state, e.g. valve operation
Corrected pulse
Used for proving, see paragraph 10. Only available on output 1.
5 .1 .6 .1 Pulse output
Figure 34 Configure pulse outputs
• Select the variable from the pull down ID data tree. This would normally be a counter incre-
ment value.
• The divisor is used to divide the counter increment. So use 10 to have an output of 50Hz for
500 increments per second.
• Select the maximum frequency of the output, from 50 to 2 Hz.
• Select the duty cycle from 25%, 50% or 75%. This means that e.g. 25% of the time the signal
will be raised, the other 75% it will be low. Typically 50% will be chosen.
• It is possible to reverse the logic (invert high and low) of each output by enabling the Invert
tick box.