The capacity limits are based on a percentage of the high and low flow as entered in the flow

rates and totals page of the stream.

NOTE: Each stream must be assigned a different priority.

7 .3 .2 Valve control

Run switching can automatically open and close the following valves of a stream:

• Inlet valve

• Outlet valve

• Prover valve

Please note that these valves are specifically used for run switching and do not need to be con-

figured anywhere else and that they are independent of any valve used under “Valves”.

For each of them the following configuration is needed:

Figure 128 Stream run switching valve control

Control valve Control setting for the

stream valve
Not used

The valve will not be used by run switching

Monitored

Run switching will only monitor, not control the valve.

Fully controlled

Run switching will actively control the valve

Alarms

Select whether an alarm should be given when the valve cannot

be switched. This is particularly important when control valve

is monitored.

Open/ close duration keypad

Length of time the open and close the valve signal is sent

Transition duration keypad

The maximum time the valve may move before an alarm is

raised

7 .3 .3 Flow control valve

A PID valve per stream to control the flow of the medium based on PID setpoints. Please note

that this valve is specifically used for run switching and does not need to be configured any-

where else and that it is independent of any PID valve used under “Valves”.