ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 110

Modbus Parameters

59407, Issue 1 – March 2008

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

16

Profile Running

17

Profile Ended

Value

Backlight Colour

0

Green to Red on Alarm

1

Red to Green on Alarm

2

Permanent Green

Backlight Colour

7668

0x1DF4

R/W

3

Permanent Red

Value

Language

0

Main Display Language

Display Language

7675

0x1DFB

R/W

1

Alternate Display Language

Display Contrast

7676

0x1DFC

R/W

0 to 127
Value

Invert Display

0

Normal Display

Invert Display

7677

0x1DFD

R/W

1

Inverted Display

Setup Lock Code

7678

0x1DFE

R/W

1 to 9999. Default is 10

Configuration Lock
Code

7679

0x1DFF

R/W

1 to 9999. Default is 10

Tuning Lock Code

7680

0x1E00

R/W

1 to 9999. Default is 10

Supervisor Lock
Code

7681

0x1E01

R/W

1 to 9999. Default is 10

Profiler Lock Code

7682

0x1E02

R/W

1 to 9999. Default is 10

USB Lock Code

7683

0x1E03

R/W

1 to 9999. Default is 10

Recorder Lock Code

7684

0x1E04

R/W

1 to 9999. Default is 10
Value

Read Only Operation Mode

0

Operation Mode Read/Write

Read Only
Operation Mode

7685

0x1E05

R/W

1

Operation Mode Read Only

Value

Bar Graph Format

0

Power Output

1

Control Deviation

Bar Graph Format

7686

0x1E06

R/W

2

% Memory Remaining

Value

Trend Sample Interval

0

Every Second

1

Every 2 Seconds

2

Every 5 Seconds

3

Every 10 Seconds

4

Every 15 Seconds

5

Every 30 Seconds

6

Every Minute

7

Every 2 Minutes

8

Every 5 Minutes

9

Every 10 Minutes

10

Every 15 Minutes

Trend View Sample

Interval

9000

0x2328

R/W

11

Every 30 Minutes