Segment data, Read profile name – West Control Solutions ProVU 4 User Manual

Page 126

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Modbus Parameters

Page 125

Segment Data

The Segment Data is included in the response to a Read Segment request. It is provided in
two parts (Segment Info A and B).
The meaning of the data contained in Segment Info A and B depends on the type of segment
it relates to. Null is shown for unused data, this can be any value.

Segment Info

Segment
Type

A

B

Description

Ramp Time

Time

Target setpoint

Ramp to the target setpoint “B” in the time “A”

Ramp Rate

Ramp rate

Target setpoint

Ramp to the target setpoint “B” at the ramp rate “A”

Step

Null

Target setpoint

Step to a target setpoint “B”

Dwell

Dwell time

Null

Stay at the current setpoint for a period of time “A”

0 = Operator

Null

Wait for the operator to release the hold

1 = Time of day

Start Time

Wait until time of the day “B” in seconds since
midnight. (recorder only).

2 = Aux A digital
input

Null

Wait for digital input A signal

Hold

3 = Aux B digital
input

Null

Wait for digital input B signal

Loop

Number of times to
repeat 1 to 9999

Segment number

Loop to the specified segment number “B” from this
point. Repeat this “A” times. Only segments below
the current segment can be entered. Two loops
must not cross each other.

Join

Null

Profile number

On completion of this profile jump run profile “B”

0 = Control off

Null

Turn off all control outputs.

1 = Maintain profile
setpoint

Null

Stay at the final setpoint of the profile

End

2 = Use controller
setpoint

Null

Use the active controller setpoint.

0 = Outputs off

Repeat the profile sequence number “B” times,
then turn off the control outputs

1 = Maintain profile
setpoint

Repeat the profile sequence number “B” times,
then hold the last profile setpoint.

Repeat
Sequence
Then End

2 = Use controller
setpoint

Number of times to
repeat sequence

Repeat the profile sequence number “B” times,
then use the active controller setpoint.

Read Profile Name

This command returns the name of the profile defined by the profile number requested.

Read Profile Name - Request (to instrument)

Field Name

Data

Comments

(Dec)

(Hex)

Unit Address

A/R

A/R

The ID address of the instrument as
required

Function Code

23

17

Requires the multi read/write function

Read Start Address High Byte

32

20

Read Start Address Low Byte

06

06

Read Quantity Of Registers High Byte

00

00

Read Quantity Of Registers Low Byte

08

08

Write Start Address High Byte

32

20

Write Start Address Low Byte

06

06