Profile Cycles & Repeat Sequences

A profile can be configured to run itself 1 to 9999 times or continuously using the Profile
Cycles setting. A profile ending with Repeat Then End will run the entire sequence of
profiles again 1 to 9999 times or continuously.

PROFILE 4

PROFILE 31

PROFILE 7

Join (Profile 4 to Profile 31)

Join (Profile 31 to Profile 7)

Figure 43.

Profile Cycles & Repeats

Power/Signal Lost Recovery Actions

If there is a power cut while a profile is running, the instrument will use the defined Profile
Recovery Method
once the power has been restored.

If there is a break in the input while a program is running, the unit will go to the Pre-Set
Power Value during the break condition. Once the condition has ended it carries out the
same recovery action as specified for power failure.

Note:

Recorder versions always use option E (Continue profile from the point it had reached
when the power failed) if the Power Off Time is less than the Profile Recovery Time
setting. If the power is off for more than this time, the defined Profile Recovery Method is
used.

Example:
Runs profile 4 once,
profile 31 three times
& profile 7 once.
This sequence is
repeated ten times.

Profile 31

Cycles = 3

Repeat Sequence = 10

Repeat Then End

(times to repeat = 10)

Profile 4

Cycles = 1

Profile 7

Cycles = 1