Digital inputs, Digital input performance – West Control Solutions ProVU 4 User Manual

Page 175

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 174

Specifications

59407, Issue 1 – March 2008

Input resistance:

mV ranges : >10MΩ.
Voltage ranges: 47KΩ.
Current ranges: 5Ω.

Input protection:

Voltage input: will withstand up to 5x input voltage overload without
damage or degradation of performance in either polarity.
Current input: will withstand 5x input current overload in reverse
direction and up to 1A in the normal direction.

Isolation:

Reinforced safety isolation from outputs and inputs (except to Digital
Input B).

Sensor Break
Detection:

Applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only.
Control goes to the pre-set power value if Auxiliary Input is providing the
active setpoint source.

Digital Inputs

Digital Input Functions

Function

Logic High

Logic Low

Profile Run/Hold

Hold Running Profile

Run or release selected profile

Hold Segment Release

Release from Hold Segment

No Action

Profile Abort

Abort Running Profile

No Action

Data Recorder

Stop Recording

Start Recording

Internal Setpoint Select

Select Local Setpoint 1

Select Alternate Setpoint

Auto/Manual Control

Automatic Control Mode

Manual Control Mode

Control Outputs

Enable PID Control Outputs

Disable PID Control Outputs

Digital Input Performance

Type:

Voltage-free or TTL-compatible.

Voltage-Free Operation:

Connection to contacts of external switch or relay:
Open = Logic High. Minimum contact resistance = 5KΩ,
Closed = Logic Low. Maximum contact resistance = 50Ω.

TTL levels:

2.0 to 24VDC = Logic High.
–0.6 to 0.8VDC = Logic Low.

Digital Input Sensitivity:

Edge Sensitive. Requires High-Low or Low-High transition to
change function.

Response Time:

Response within <0.25 second of signal state change.

Isolation:

Reinforced safety isolation from inputs and other outputs.

Advertising