Power connections, Power connections - mains powered instruments – West Control Solutions ProVU 4 User Manual

Page 27

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 26

Wiring Instructions

59407, Issue 1 – March 2008

13

14

L

N

The wiring diagram below shows the additional connections (numbered 25 to 42) at the
sides of the case rear. These are required for Options Slots 4 and C if fitted.

Figure 8. Additional Option terminals

Note:

Use single strand (1.2mm / AWG18 max size) copper wire throughout, except for the
thermocouple input, where the correct thermocouple or compensating cable and
connectors must be used.

Power Connections

Power Connections - Mains Powered Instruments

Mains powered instruments operate from a 100 to 240V (±10%) 50/60Hz supply. Power
consumption is 20VA. Connect the line voltage (live and neutral) as illustrated via a two-pole
IEC60947-1 & IEC60947-3 compliant isolation switch / circuit breaker and a UL listed fuse
type: 250V AC 1Amp anti-surge. If the instrument has relay outputs with contacts carrying
mains voltage, it is recommended that the relay contacts supply should be switched and
fused in a similar manner, but should be separate from the instruments mains supply.

Figure 9. Mains Power Connections

WARNING:

CHECK THE INFORMATION LABEL ON THE CASE TO DETERMINE THE CORRECT
VOLTAGE BEFORE CONNECTING TO A LIVE SUPPLY.

CAUTION:

This equipment is designed for installation in an enclosure that provides adequate
protection against electric shock. The isolation switch should be located in close
proximity to the unit, in easy reach of the operator and appropriately marked.

Advertising