Input configuration sub-menu – West Control Solutions ProVU 4 User Manual

Page 50

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Configuration & Use

Page 49

Input Configuration Sub-Menu

Table 9. Input Configuration Sub-Menu Screens

Input Configuration:

Process Variable Input
Type

w From Thermocouple, RTD and Linear inputs. - see specifications

section for full details of input types available.

Engineering Units

w Select display units from: °C; °F; °K; bar; %; %RH; pH; psi or none.

Decimal Point Position

w Sets the maximum display resolution to 0; 1; 2 or 3 decimal places.

Temperature inputs are limited to 0 or 1 place. Numbers >99.999
never display more than 2 dec places, >999.99 never display more
than 1 dec place and >999.99 always display without decimal places.

Multi-Point Scaling
Enable

Enables or disables Linear Input Multi-Point Scaling. This feature
allows up to 15 point linearization of mA or V DC input signals.

Scale Range Lower
Limit

w

Multi-Point Scale
Point(s)

Scale Range Upper
Limit

w

For Temperature inputs, Upper & Lower Limits set the usable span.
Min = 100 units, max = range limits - see specs. For Linear inputs,
Upper & Lower Limits define the values shown (-1999 to 9999) when
input is at minimum and maximum values. Min span = 100 units. If
Multi-Point Scaling enabled, up to 15 breakpoints* can scale input vs.
displayed value between the linear input scale limits.
*A breakpoint set at 100% input ends the sequence.

CJC Enable/Disable

Enables/disables internal Thermocouple Cold Junction
Compensation. The default value is Enabled.

Process Variable Offset

Trims the process value. +Ve values add to, –Ve values subtract
from measured input.

Caution:

A value other than zero alters the

apparent calibration of the instrument. Use with care!

Input Filter Time

Removes unwanted signal noise. Adjustable from 0.0 to 100.0
seconds or OFF (default = 2s).

Caution:

Too large a value will cause

slow response to changes in the process. Use with care!

Auxiliary Input n Type

w Sets the type of signal to be connected to the auxiliary inputs (if

fitted). From: 0-10V; 2-10V; 0-5V; 1-5V, 0-20mA or 4-20mA DC.
Auxiliary input B also supports >2K Potentiometer and 0-100mV.

Auxiliary Input n Scaling
Lower Limit

w Scales the displayed a value (-9999 to 10000) when an auxiliary

input is at or below it’s lower limit (e.g. 4mA for a 4-20mA signal).

Auxiliary Input n Scaling
Upper Limit

w Scales the displayed a value (-9999 to 10000) when an auxiliary

input is at or above it’s lower limit (e.g. 20mA for a 4-20mA signal).

Auxiliary Input n Offset

Trims the displayed a value for auxiliary input A or B. +Ve values are
added to, –Ve values subtracted from the measured auxiliary input.

Calibration Reminder
Enable/Disable

Enables or disables the display of Calibration Reminder at start-up
(repeated daily thereafter), if the due date has passed – Available on
the Recorder version only

Calibration Reminder
Due Date

Sets the due date for the Calibration Reminder - Available on the
Recorder version only

Advertising