Press

to select the Setpoint Value Display and Adjustment screen

Press

or

to adjust each Local Setpoint to the required value.

A Remote Setpoint value cannot be altered from the key pad.

Adjusting the Setpoint Ramp Rate

The Setpoint Ramp Rate may be adjusted in the range 0.1 to 9999.0 (in display units per
hour) and OFF. When the Setpoint Ramp Rate is set to Off, setpoint changes will step
immediately to the new value.

Press

to select the Setpoint Ramp Rate screen

Press

or

to adjust ramp rate to the required value

.

Note:

The SETPOINT ramp feature disables the pre-tune facility. The self-tune facility will
calculate new tuning terms only after the SETPOINT has completed the ramp.

Selecting Automatic or Manual Mode

Depending on the Control Configuration settings, an Auto/Manual selection screen may be
shown which allows operators to select between automatic or manual control. Switching to or
from manual mode is made via Bumpless Transfer. In Manual mode the Setpoint display is
replaced by a 0 to 100% power output level, labelled “Man”.

Press

to select the Manual Power screen

Press

or

to adjust required power to the required value

.

Note:

In Manual mode a running profile will hold until automatic control is reselected.

CAUTION:

The Manual Mode power level can be adjusted from 0 to 100% (-100 to +100% for
dual control). It is not restricted by the Output Power Limit parameters.

Control Enable or Disable

Depending on the Control Configuration settings, a Control Enable/Disable screen may be
show. Disabling control turns of all control outputs (Primary and Secondary power output
levels are set to zero).

Press

to select the Control Enable screen

Press

or

to change between control enable and disable.

CAUTION:

Use with care. The instrument is not able to control the process when control is
disabled. The Output Power Lower Limit parameters are also ignored.