Output configuration sub-menu – West Control Solutions ProVU 4 User Manual

Page 53

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

Page 52

Configuration & Use

59407, Issue 1 – March 2008

Setpoint Ramp Rate

The Setpoint Ramp Rate value (1 to 9999 display units per hour or
OFF). This ramp is applied at power-up and any setpoint changes.

Local Setpoint 1 Value

w Sets the value of Local Setpoint 1 between the Setpoint Upper and

Lower Limits.

Local Setpoint 1 Offset

A value added to the Setpoint 1 value (+ve values) or subtracted
from it (-ve values). Use when the instrument is a slave in multi-zone
applications to achieve a zone offset. Otherwise, always set to zero.

Local Setpoint 2 Value

w Sets the value of Local Setpoint 1 between the Setpoint Upper and

Lower Limits.

Local Setpoint 2 Offset

A value added to the Setpoint 2 value (+ve values) or subtracted
from it (-ve values). Use when the instrument is a slave in multi-zone
applications to achieve a zone offset. Otherwise, always set to zero.

Output Configuration Sub-Menu

Table 11. Output Configuration Sub-Menu Screens

Outputs Configuration:

No Outputs Warning

Shown if the Outputs Configuration menu is entered on an
instrument without any output modules fitted.

Linear Output n Type

w

Set the desired type for any Linear Outputs fitted. From: 0-5, 0-10,
1-5, 2-10V & 0-20, 4-20mA or 0-10VDC adjustable Transmitter PSU.

Adjustable 0-10V
Transmitter PSU n

w

Sets the voltage required if Linear Output n type is 0-10VDC
adjustable Transmitter PSU.

Output n Usage

w

Sets the use for each output fitted. From: Primary or Secondary
Control; Alarms; Profile Events & Alarms; Retransmit Process
Variable or Setpoint. Choices offered are as appropriate for the
output type fitted (e.g. only Linear Outputs can retransmit).

Output n Alarm
Selection

w

When an Output Usage is Alarms, this selects which alarm(s) will
cause it to change state. From Alarm 1; 2; 3; 4; 5 or a Logical OR of
alarms 1 to 2; 1 to 3; 1 to 4 or 1 to 5. Each choice is selectable with
Direct Action (on during alarm) or Reverse Action (off during alarm).

Output n Events

w

When and Output Usage is Events & Alarms, this selects which
Events(s) will cause it to change state. From: Profile Running or
Profile End; Event 1; 2; 3; 4; 5 or a Logical AND of Event n & Alarm
n. Each choice is selectable with Direct Action (on during event) or
Reverse Action (off during event). - Profiler version only

Retransmit Output n
Scale Low

w

Sets the displayed value at which a retransmission output should be
at it’s minimum level (e.g. the display value when a 4 to 20mA PV
Retransmission output will be 4mA. Adjustable from -1999 to 9999.

Retransmit Output n
Scale High

w

Sets the displayed value at which a retransmission output will be at
it’s maximum level (e.g. the display value when a 4 to 20mA PV
Retransmission output will be 20mA. Adjustable from -1999 to 9999.