Option slot 2 parameters – West Control Solutions ProVU 4 User Manual

Page 90

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Modbus Parameters

Page 89

Option Slot 2 Parameters

Parameter Name

Modbus Address

Access

Values

(Dec)

(Hex)

Value

Module Fitted In Slot 2

0

None Fitted

1

Single Relay

2

Single SSR Driver

3

Linear mA/V DC

8

Triac

9

Dual Relay

10

Dual SSR Driver

11

24VDC Transmitter PSU

Option Slot 2
Module Type

2160

0x0870

RO

255

Error (unrecognised module)

Value

Linear Output 2 Type

0

0 to 5V DC

1

0 to 10V DC

2

2 to 10V DC

3

0 to 20mA DC

4

4 to 20mA DC

Linear mA/V DC
Output 2 Type

2161

0x0871

R/W

5

Variable 0 to 10VDC Transmitter PSU

Value

Digital Output 2 or 2A Status

0

Inactive

Digital Output 2 or
2A Status

2162

0x0872

RO

1

Active

Value

Digital Output 2B Status

0

Inactive

Digital Output 2B
Status

2163

0x0873

RO

1

Active

Linear Output 2
Level Status

2164

0x0874

RO

-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Value

Linear Output 2 or 2A Function

0

Disabled

1

Primary Output Power

2

Secondary Output Power

3

Retransmit Actual Setpoint Value

Linear Output 2 or
2A Function

2174

0x087E

R/W

4

Retransmit Process Variable Value

Value

Digital Output 2 or 2A Function

0

Disabled

1

Primary Output Power

2

Secondary Output Power

3

Alarm

Digital Output 2 or
2A Function

2176

0x0880

R/W

4

Alarm and Event

Advertising