West Control Solutions ProVU 4 User Manual

Page 52

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Configuration & Use

Page 51

Secondary On-Off
Differential

Sets the Secondary On-Off control hysteresis (deadband) from 0.1 to
10.0% of Span (centred about setpoint), when Primary PID with
Secondary On-Off control is used.

Primary & Secondary
On-Off Differential

Sets the combined Primary & Secondary On-Off Control hysteresis
(deadband) from 0.1 to 10.0% of Span. when Primary On-Off control
and Secondary On-Off control is used.

Primary Cycle Time

Sets the Primary Power Cycle Time (0.5s to 512s). For Primary
Relay, SSR Driver or Triac Control Outputs only.

Secondary Cycle Time

Sets the Secondary Power Cycle Time (0.5s to 512s). For Secondary
Relay, SSR Driver or Triac Control Outputs only.

Primary Power Upper
Limit

Sets the Maximum Primary Output Power Limit, from 0 to 100% of
available power. This value must be higher than the lower limit.

Caution:

The instrument will not be able to control the process if

sufficient power isn’t available to maintain setpoint. Use with care!

Primary Power Lower
Limit

Minimum Primary Output Power limit, from 0 to 100%. This value
must be less than the upper limit.

Caution:

The instrument will not

be able to control the process if the lower limit is more than required
to maintain setpoint. Use with care!

Secondary Power Upper
Limit

Maximum Secondary Output Power limit, from 0 to 100%. This value
must be higher than the lower limit.

Caution:

The instrument will not

be able to control the process if sufficient power isn’t available to
maintain setpoint. Use with care!

Secondary Power Lower
Limit

Minimum Secondary Output Power limit, from 0 to 100%. This value
must be less than the upper limit.

Caution:

The instrument will not

be able to control the process if the lower limit is more than required
to maintain setpoint. Use with care!

Sensor Break Pre-set
Power Output

Sets the power level applied if the process input (or active RSP) is
lost. Adjustable from 0 to 100% or -100 to +100% for Dual Control.
The default value is OFF (0% power).

Caution:

Use a value that will

maintain safe conditions.

Setpoint Selection

w Sets the method to select the Active Setpoint. From: Local

Setpoint 1 only; Alternate Setpoint only; Select via Digital Input A or
B; or Operator Selectable (allows Setpoint 1 or Alternate Setpoint to
be selected from Operation Mode).

Alternate Setpoint
Source

w Up to two setpoints can be used, Local Setpoint 1 plus an Alternate

The Alternate Setpoint can be selected from: Local Setpoint 2 or a
Remote Setpoint set via Auxiliary Input A or B.

Setpoint Upper Limit

The maximum allowable setpoint value. Adjustable within the Input
Span limits, but must be greater than the Setpoint Lower Limit.
Applies to both local and remote setpoints.

Caution:

Operators can

adjust the setpoint to any value between the Setpoint Upper and
Lower Limits. Use with care!

Setpoint Lower Limit

The minimum allowable setpoint value. Adjustable within the Input
Span limits, but must be less than the Setpoint Upper Limit. Applies
to both local and remote setpoints.

Caution:

Operators can adjust

the setpoint to any value between the Setpoint Upper and Lower
Limits. Use with care!

Setpoint Ramp Editing

Enables or disables the changing of the Setpoint Ramp Rate in
Operation Mode – Note: this does not turn off an active ramp. To
turn of an active ramp, set the Setpoint Ramp Rate to OFF.

Advertising