Profile end actions – West Control Solutions ProVU 4 User Manual

Page 72

Advertising
background image

ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Profiler Option

Page 71

Possible Recovery Methods:

A Abort the profile and maintain the profile value from the time the power failed.
B Abort the profile and use Controller Setpoint value.
C Abort the profile with the Control outputs off.
D Restart the profile again from the beginning.
E Continue profile from the point it had reached when the power failed

Figure 44.

End, Abort and Recovery Actions

Profile End Actions

Once a running profile ends, that profiles’ Segment End Type defines action taken by the
instrument. If a sequence of profiles has been completed, the End Segment Type of the last
profile will be carried out. The possible end actions are explained below.

Possible Profile End Actions:

A At profile end, maintain the Final Setpoint value of the last segment.
B At profile end, exit Profiler Mode and use the Controller Setpoint value.
C At profile end, remain in Profiler Mode with the Control outputs off.

Figure 45.

Profile End Action

Controller SP

Run
(Start-on SP)

Power Off

Power On

= Control Off

Planned Profile

Power Off Time

Controller SP

Run
(Start-on SP)

Normal Profile End

= Control Off

Last Profile SP

Controller SP