ProVU4 Controller, Profiler & Recorder/Controller - Product Manual

59407, Issue 1 – March 2008

Manual Tuning

Page 75

5. Follow the instructions in the diagram below. At each stage, allow sufficient settling time

before moving on to the next stage. P.Pb is the Primary Proportional Band, Int.T is the
Integral Time Constant.

Table 26. Manually Tuning Valve Control

Time

Process Variable

T

b

Time

Process Variable

T

a

START

Apply Power to

the load.

Does the

PV

continuously

Oscillate?

Note the time

interval T

a

Set

P.Pb

= 0.8%

Set

Int.T

= T

a

Are the

Oscillations

decaying to

zero?

Multiply

P.Pb

setting by 1.5

END

Note the period

of the decaying

oscillations (T

b

)

Multiply

P.Pb

setting by 1.5

Set

Int.T

= T

b

2

No

Yes

Yes

No

The controller is now tuned.

Fine-tuning may be required

to optimise the controllers

response