DC Linear Input

DC Linear Types & Ranges

Input
Type

Ranges

Input
Type

Ranges

mA DC

0 to 20mA

4 to 20mA

0 to 5V

1 to 5V

mV DC

0 to 50mV

10 to 50mV

V DC

2 to 10V

0 to 10V

DC Linear Performance

Display Scaling:

Scalable up to –9999 to 10000 for any DC Linear input type.

Minimum Span:

100 display units.

Decimal Point
Display:

Decimal point selectable from 0 to 3 places, but limits to 5 display digits
(e.g. values > 99.9 have no more than 2 decimal places).

DC Input Multi-Point
Linearization:

Up to 15 scaling values can be defined anywhere between 0.1 and 100%
of input.

Measurement
Accuracy:

0.1% of span 1LSD.

Maximum Overload:

1A on mA input terminals, 30V on voltage input terminals.

Sensor Break
Protection:

Applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only.
Break detected within two seconds. Process Control outputs go to the
pre-set power value. Low and Senor Break Alarms operate.

Auxiliary Inputs

Auxiliary Input Types & Ranges

Input
Type

Ranges – Auxiliary Input A

Input
Type

Ranges – Auxiliary Input B

mA DC

0 to 20mA

4 to 20mA

mA DC

0 to 20mA

4 to 20mA

0 to 5V

1 to 5V

0 to 5V

1 to 5V

V DC

2 to 10V

0 to 10V

V DC

2 to 10V

0 to 10V

mV DC

0 to 100mV

10 to 50mV

Pot

2KΩ or higher

Auxiliary Input Performance

Input Sampling rate:

4 per second.

Input Resolution:

16 bit ADC.

Auxiliary Input
Scaling:

Scalable as a Remote Setpoint (RSP) input between –9999 and 10000,
constrained by the Setpoint Limits.

Measurement
Accuracy:

0.25% of input span 1 LSD.