System configuration, System configuration 10 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 10

Advertising
background image

System Configuration

Version 4…20 mA without communication: Connection as traditional point-to-point connection according to the known

regulations of the measuring & control techniques
HART version: When using ‘Communication’ (an AC signal which modulates on the 4-20 mA signal), make sure the

connected outputs, buffer amplifier and barriers are compatible with the frequency ranges used In addition to the load,

the AC impedance requirements must be met Therefore, it is recommended that only the specified amplifier, barrier and

configuration device be used
To prevent crosstalk between lines and reduce disturbances through electromagnetic influences, use twisted-pair shielded

lines with a diameter of AWG 22…14 (0 3…2 5 mm

2

) and a maximum capacity of 100 pF/m

The line capacities and connected devices may not exceed the maximum values listed for a particular HART protocol
All components that are connected to the SRD in an explosion hazardous area require an Ex-Approval The applicable limit

values must not be exceeded Comply with the limit values when connecting additional capacitances, inductances, voltage or

current sources

Summary – Hart and 4…20 mA without Communication

Page 10

August 2014

POS-UM-00010-EN-03