Setting the Travel Indicator

The mechanical travel indicator is coupled to the feedback shaft of the positioner by a gear The gear has two selectable

ratios

1)

1 : 2 and 1 : 6

1)

The values are rounded for making easier calculations The exact ratios are 1 : 1 83 and 1 : 6 28

Selecting Gear Ratio

For rotation angles of the feedback shaft less than 30° select a ratio 1 : 6 This gear selection amplifies the feedback shaft

rotation angle six times and for example, a 20° angle is shown as 120°
For rotation angles greater than 30° select a ratio of 1 : 2 This gear selection amplifies the shaft rotation angle by a factor of

two and for example, a 45° angle is shown as 90°
For rotary actuators the rotation angle is equal to the rotation angle of the actuator Consequently, a 90° rotation angle will

result in a 180° display angle for the 1 : 2 gear ratio
For linear actuators the rotation angle is determined by travel span and feedback lever length In this case, an exact 180°

display angle can only be achieved for a 30° rotation angle using a 1 : 6 gear ratio If any other rotation angle results, either the

closed or full open position can be set to be indicated at, for example 0° or 180° However, if the closed position is chosen for

display, then the full open display position angle is dependent on travel span, feedback lever length and gear ratio If the full

open position is chosen for display, then the closed position angle becomes dependent
Setting Gear Ratio
Remove the travel indicator 12 Pull out the pin 12b for a ratio 1 : 2 or push in the pin for a ratio 1 : 6 Use a smooth turning

operation to free the gears and to set the pin 12b against the stop See illustration

Figure 23:

Turn the travel indicator 12 to the desired position, put it on the gear shaft against the stop and pinch the wire ring for

secure coupling

DECOMMISSIONING

Before decommissioning the unit, disconnect the supply air and the electrical input signal
After disconnecting the electrical input signal the last confirmed configuration of the positioner is preserved in the memory

Exchange of Device

If a temporary decommissioning of the SRD and a later mounting to another actuator has to be carried out, before

disconnecting, we recommend to Reset Configuration in Menu 9 1 So the default settings ”Ex-Factory” are reactivated This

facilitates a later recommissioning

Decommissioning

Page 66