Foxcom communication, With communication profibus-pa, With communication foundation fieldbus – Badger Meter SRD/SRI Valve Positioners User Manual

Page 75

Advertising
background image

HART

measured at
configurator:

measured at

SRD:

Configurator
transmits

at least

350 mVpp

at least

120 mVpp

SRD991
transmits

at least

120 mVpp

at least

400 mVpp

FoxCom Communication

When using the ‘communication’ (a rectangular signal which is modulated onto the constant current signal), make sure the

connected outputs are suitable for the used frequency ranges The supply instrument must be a voltage source with an

impedance of 250…500 Ohm The total of all instrument and lead capacities must be <60 nF It is recommended therefore, to

use only suitable instruments
To eliminate crosstalk between leads and to reduce disturbances through electromagnetic influences, use twisted paired

shielded leads (0 3…2 5 mm

2

, max 100 pF/m)

The capacities of the leads and the connected instruments must not exceed the maximum values for FoxCom
All components which are connected to the SRD in an explosion hazardous area, require an Ex-Approval The applicable

limit values must not be exceeded in any case These limit values also have to be adhered to when connecting additional

capacitances, inductances, voltages and currents
Measuring FoxCom Communication Signal
If a reliable communication signal cannot be received, it is advisable to check the level with an oscilloscope The first data

block always comes from the configurator and the second block is the reply from the SRD

FOXCOM

measured at
configurator:

measured at

SRD:

Configurator trans-
mits (Request)

at least

350 mVpp

at least

75 mVpp

SRD transmits
(Acknowledge)

at least

75 mVpp

at least

350 mVpp

With Communication PROFIBUS-PA

The operation of the positioner takes place digitally, as per PROFIBUS-PA Profile Class B according to EN 50170 and DIN

19245 part 4 Data transmission via bit synchronous current modulation with a speed of 31250 bits via twisted and

shielded two-wire connections according to IEC 1158-2, with cable shields on both sides and bus terminators according to

recommendation IEC 1158-2
The positioner has to be connected to a segment coupler, which has to be conforming to IEC 1158-2 For operation in

explosion hazardous areas, a segment coupler in explosion proof version has to be used Supply as well as communication

takes place via the bus
All components which are connected to the SRD in an explosion hazardous area, require an Ex-Approval The applicable

limit values must not be exceeded in any event These limit values also have to be adhered to when connecting additional

capacitances, inductances, voltages and currents The FISCO model is thereby used as a basis
Further information for observance:

”Technical Guide for PROFIBUS-Connection Technique” PROFIBUS-User Organization, Order no 2 141

With Communication FOUNDATION Fieldbus

The operation of the positioner takes place digitally, as per FOUNDATION Fieldbus Specification Rev 1 4 Data transmission via

bit synchronous current modulation with a speed of 31250 bits of via twisted and shielded two-wire connections according to

IEC 1158-2, with cable shields on both sides and bus terminators according to recommendation IEC 1158-2
The positioner has to be connected to components which are conforming to IEC 1158-2 For operation in explosion hazardous

areas, an Ex-separator has to be used Supply as well as communication takes place via the bus

System Configuration

Page 75

August 2014

POS-UM-00010-EN-03