ELECTRICAL CONNECTION

TO AVOID ANY ELECTRICAL SHOCK, RESPECT THE MAXIMUM INPUT SUPPLY VOLTAGE FOR THE DEVICE AND OPTIONS.

TO AVOID ANY PERSONAL INJURY OR PROPERTY DAMAGE FROM SUDDEN OR FAST MOVEMENT, DURING ELECTRICAL

CONNECTION: DO NOT PUT YOUR FINGER OR OTHER PART AT ANY TIME INSIDE THE VALVE OR IN ANY MOVING PART

OF THE ACTUATOR. DO NOT PUT YOUR FINGER OR OTHER PART AT ANY TIME IN THE FEEDBACK LEVER MECHANISM.

DO NOT TOUCH THE REAR PART OF THE POSITIONER AT ANY TIME.
Unused cable glands should be closed off
Feed in the bus cable through the gland 1 The gland is suitable for cable diameters of 6…12 mm (0 24…0 47 in) Observe the

tightness of the cable entry
Make the electrical connection of the input line at the screw terminals 3b, whereby with fieldbus devices no polarity has to be

observed The terminals are suitable for wire cross-sections of 0 3…2 5 mm

2

(22 -14 AWG)

The shield of the bus connection is
• with conductive cable glands (recommended) directly connected with the housing
• with non-conductive cable glands to be placed onto the inner screw terminal 4

NOTE:

N

When connecting shielded cable, connect the cable shield on both sides (on the positioner as well as on the system

side) For selection of cable, see recommendation for cable types according to IEC 1158-2

For connection to a local ground, use the internal and external ground terminal 4
Test sockets for measuring purposes are integrated into the connecting terminals With version HART or FoxCom at clamps

11+ and 12– a handheld terminal or modem for communication can be attached

Electrical Connection

Page 34

August 2014

POS-UM-00010-EN-03