Messages

In the SRD with the “Built-in pressure sensors” option, flashing is superimposed by a flickering

LEDs

Description of message / LCD text

Remedy

M

1

2

3

4

¾ ¼

-

-

-

Message 1:
write protection

Parameter and functions are write-protected

Can be changed via Configurator, FDT/DTM Soft-
ware or Profile 3.0 (PROFIBUS)

M

1

2

3

4

¾

-

¼

-

-

Message 2:
Parameter

Invalid, undefined parameter values

Reset of configuration to factory setting in Menu
9.1

M

1

2

3

4

¾ ¼ ¼

-

-

Message 3:
Calibration

Incomplete calibration or entering value resp.
calibration value outside of permissible tolerance
range

Repeat calibrations in Menus 9.2 ... 9.5

M

1

2

3

4

¾

-

-

¼

-

Message 4:
Input current outside
of operating range

Check nameplate (INPUT) for correct version
Message appears at :

Analog or HART: input current under approx. 3.8

mA or above approx. 22 mA

Fieldbus or FoxCom: input current under approx.

9 mA or above approx. 12 mA

check supply voltage (Analog) or
check Bus voltage (Fieldbus),
exchange SRD if necessary

M

1

2

3

4

¾ ¼

-

¼

-

Message 5:
Position sensor

Positioner already ca-
librated, dismonted
and supply. If you
supply (4-20 mA or
with a fieldbus) a po-
sitioner not mounted
and bring the poten-
tiometer out of range,
the message will ape-
ar and remain till the
potentiometer goes
again in range and
the error is validate
with push button.

Position sensor input recognizes error

check 3-pole plug at electronic board
check cable to sensor
check sensor (Potentiometer: 5k +20% –0%)

Position not within permissible rotation angle range.
Lower deviation of the original 0% and exceeding
of the original 100%, which have been determined
by Autostart.

Check feedback lever mounting (flat area points to
arrow on housing)

During Autostart a change of the direction of mo-
vement was found

Acknowledge with UP+DOWN keys, then o.k.

Check further possible reasons:
valve seat worn-out; spindle lock out-of-line; carrier
unit on spindle lock is damaged (for determination of
valve position).

M

1

2

3

4

¾

-

¼ ¼

-

Message 6:
I/P-converter output

Connection I/P converter to electronic board faulty check 2-pole plug at electronic board

check cable to the I/P converter
check I/P converter to detect short circuit or inter-
ruption

M

1

2

3

4

¾ ¼ ¼ ¼

-

Message 7:
Air supply /
pneumatic error

Detection:
spring closes: w > 2 %, but position < 1 %
spring opens: w < 98 %, but position > 99 %
without spring:
no actuator change in direction of position signal

check air supply pressure
lead cable separated
possibly poor control parameters are set
pneumatic parts blocked

Troubleshooting Guide