9.6 Resetting of Configuration and Calibration to “ex factory” settings
For the exchange of the electronics the device must be configured
whether the pneumatic output is single-acting or double-acting so that the
controller shows the correct behavior during the next start-up.

Caution: The current calibration for inputs and outputs, the angle calib-
ration and all other calibrations are reset to their factory defined condition!

9.6 Resetting of Configuration and Calibration to “ex factory” settings

– for single-acting pneumatic output

-

-

-

-

1

LED 4 lights up

The factory calibration for single-acting pneumatic output is restored when
pressing UP+DOWN keys simultaneously.

9.7 Resetting of Configuration and Calibration to “ex factory” settings

– for double-acting output

-

1

-

-

1

LED 1 and LED 4 lights up

The factory calibration for double-acting pneumatic output is restored when
pressing UP+DOWN keys simultaneously.

9.8 Go Online without Autostart
In principle, the first startup runs an Autostart in which the SRD is optimally
adapted to the actuator, then the SRD goes online and begins to regulate.

This service function sets the SRD directly online, without an Autostart.

Only for test purposes. Not recommended for regular use.

9.9 Selection of menu language

1)

One of three of the programmed languages can be selected (only with
version with LCD display)

Ex-factory the active language is always English. Changing to one of the
other two languages, can also take place during operation.

The third menu language can be selected and was already programmed in
the factory according to customer order. If a different third menu language
is desired, then the language file can be downloaded from our website:

http://www.foxboro-eckardt.eu/download/PLFselector.html

Thereafter download the file from the PC via FDT/DTM-Software onto the
SRD. See also references on the internet page.

9.10 LCD Orientation

1)

Display normal or turned by 180°.

9.11 Calibration of Option "Position Feedback 4-20 mA"
Connect 24 V DC to the terminals of this option and insert a
precise ampmeter into this loop.

Selecting "Cal. 4 mA" should result a current of 4 mA.
Calibrate with keys UP or DOWN. Confirm with keys UP+DOWN.

Selecting "Cal. 20 mA" should result a current of 20 mA.
Calibrate with keys UP or DOWN. Confirm with keys UP+DOWN.

1)

The menus 9.8 and 9.9 appear automatically at initial start-up, i.e. if the SRD is connected
the first time to the electrical supply.

Configuration functions for all SRD versions with LCD