System configuration, System configuration 77 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 77

Advertising
background image

Communication HART

and ATEX Certification

Electrical classification

1) 2)

(Electronics family AI 638 per EC- Certificate of

Conformity PTB 00 ATEX 2128)

see Certificates of Conformity EX EVE0105 A

Type of protection ATEX “intrinsic safety”

. . . . . . . . . . . . . . . . . II 2 G EEx ia IIB/IIC,

II 2 G EEx ib IIB/IIC

Temperature classes

Type AI638 HH . . . . . . T4, Model Code EA4
Type AI638 GH . . . . . . T6 / T4, Model Code EAA

Certificate of Conformity . . . . PTB 00 ATEX 2128
For use in hazardous areas in circuits certified as intrinsic-
ally safe with the following maximum values:
Input circuit:
Ui = 30 V, Ii = 130 mA, Pi = 0.9 W
Li = 5 µH, Ci = 1.3 nF (5.3 nF to earth)

Ambient temperature ranges:
Temperature class T4: . . . . . .–40 °C to + 80 °C
Temperature class T6: . . . . . .–40 °C to + 55 °C

Explosion protection Zone 2

It is recommended to use the positioner with explosion pro-
tection “intrinsically safe” (consider temperature class).
In the Federal Republic of Germany these positioners may
be operated in Zone 2 with non-intrinsically safe circuits if
the operating values do not exceed the maximum reference
values.

Type of protection FM “intrinsic safety”

(Electronics family per BIM 638 (GH))
Cl. I, Div 1, Gp ABCD; Cl. II, Div 1, Gp EFG; Cl. III, Div 1
hazardous locations indoor and outdoor, T6/T4,
NEMA Type 4X

Type of protection FM “non-incendive”

(Electronics family per BIM 638 (GH))
Cl. I, Div 2, Gp ABCD; Cl. II, Div 2, Gp FG; Cl. III, Div 2
hazardous locations indoor and outdoor, T6/T4,
NEMA Type 4X

Type of protection CSA “intrinsic safety” *)

(Electronics family per CSA xxx)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)

*)

In preparation

1)

With appropriate order only

2)

National requirements must be observed

Communication PROFIBUS-PA

and FOUNDATION Fieldbus H1

Electrical classification

1) 2)

(Electronics family AI 638 per EC- Certificate of

Conformity PTB 00 ATEX 2128)

see Certificates of Conformity EX EVE0105 A

Type of protection ATEX “intrinsic safety”

. . . . . . . . . . . . . . . . . II 2 G EEx ia IIB/IIC,

II 2 G EEx ib IIB/IIC

Temperature classes

Type AI 638 GP/GQ, Rev 2.0, T6 / T4, Model Code EAA

Certificate of Conformity . . . . PTB 00 ATEX 2128
For use in hazardous areas in circuits certified as intrinsic-
ally safe with the following maximum values:
Input circuit:
Ui = 24 V, Ii = 380 mA, Pi = 5.32 W
Li = 5 µH, Ci = 1.3 nF (5.3 nF to earth)

Ambient temperature ranges:
Temperature class T4: . . . . . .–40 °C to + 80 °C
Temperature class T6: . . . . . .–40 °C to + 55 °C

Explosion protection Zone 2

It is recommended to use the positioner with explosion pro-
tection “intrinsically safe” (consider temperature class).
In the Federal Republic of Germany these positioners may
be operated in Zone 2 with non-intrinsically safe circuits if
the operating values do not exceed the maximum reference
values.

Type of protection FM “intrinsic safety”

(Electronics family per BIM 638 (GP/GQ, Rev.2.0))
Cl. I, Div 1, Gp ABCD; Cl. II, Div 1, Gp EFG; Cl. III, Div 1
hazardous locations indoor and outdoor, T6/T4,
NEMA Type 4X

Type of protection FM “non-incendive”

(Electronics family per BIM 638 (GP/GQ, Rev.2.0))
Cl. I, Div 2, Gp ABCD; Cl. II, Div 2, Gp FG; Cl. III, Div 2
hazardous locations indoor and outdoor, T6/T4,
NEMA Type 4X

Type of protection CSA “intrinsic safety” *)

(Electronics family per CSA xxx)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)

System Configuration

Page 77

August 2014

POS-UM-00010-EN-03